BEBCO EPS
Fuchs®Inc. • 1600 Enterprise Parkway • Twinsburg, Ohio 44087-2245 • www.bebcoeps.com
Telephone (330) 486-0002 • FAX (330) 425-4607 • E-Mail: [email protected]
8
System Mounting
IMPORTANT NOTES
Mounting LH, RH, TM, BM & WM Configurations
Mounting FM & PM Configurations
HELPFUL HINTS
FM and PM configurations are designed to mount through a panel cutout one (1) inch smaller than the overall
height and width of the system mounting plate, using clips and fasteners provided with SMK-4 or SMK-6
mounting kits. This design feature eliminates the need to drill the system mounting bolt holes in the protected
enclosure.
FM configurations are intended for mounting adjacent to the protected enclosure.
PM configurations are intended for mounting through a cutout in the protected enclosure surface.
Determine the mounting configuration of your system
using the diagrams on pages 10 & 11.
Remove and save the manila envelope (containing
the enclosure warning nameplate) which may be
taped to the outer surface of the mounting flange.
Although all purge systems are factory tested and
calibrated, we strongly suggest a bench test of basic
functions prior to installation.
The system should be mounted at EYE LEVEL.
Care must be taken to ensure the system and all
protruding components are clear of all enclosure
accesses (doors and covers) and conduit, pipe, tubing
or cable entries.
LH, RH, TM, BM and WM configurations are intended
for mounting adjacent to the protected enclosure.
LH, RH, TM & BM configurations are also suitable for
2" schedule 40 pipe mounting.
1.
Transfer panel cutout pattern to the intended surface.
2.
Check for obstructions which could prohibit bolt
fastening or system pneumatic connections.
3.
Cut panel cutout pattern on the intended surface.
4.
Deburr all cutout surfaces.
5.
Secure system to enclosure using SMK-4 or SMK-6
mounting kit, or equivalent 1/4" x 3/4" stainless steel
nuts, bolts, mounting clips and lock washers.
Surface mounting Systems
1 . Transfer hole pattern of System mounting plate to
intended surface.
2.
Check for obstructions hindering bolt fastening, drill and
ream the mounting holes before mounting the system.
3.
Secure the system to the enclosure, or other mounting
surface, using one (1) SMK-1 mounting kit or equivalent
- four (4) 1/4" x 3/4" stainless steel bolts, nuts and lock
washers.
Pipe mounting Systems
1.
Locate 2" schedule 40 pipe, (vertical for LH & RH,
horizontal for TM & BM) within five (5) feet of protected
enclosure.
2.
Ensure system is mounted in a true vertical position,
secure the system to pipe, using one (1) PMK-1 mounting
kit or equivalent - two (2) 1/4" x 2" stainless steel “U”
bolts, nuts and lock washers.
Typical Examples of Surface, Pipe, Panel & Frame Mounted Systems
Typical Surface Mounted System
(Model 1002-LPS-CI-Z-LH shown)
Typical Pipe Mounted System
(Model 1002-LPS-CI-Z-LH shown)
Typical Panel/Frame Mounted System
(Model 1002-LPS-CI-Z-PM shown)
ISC * 877-602-0010 * www.iscenclosurecooling.com