Pneumatic Tubing Requirements
Protective Gas Supply Requirements
The protective gas supply to the protection system must be
a clean, instrument quality compressed air or nitrogen and
must contain no more than trace amounts of flammable gas,
vapor or dust.
The protective gas supply compressor intake must originate
in a nonhazardous location. Suction duct passing through a
hazardous location and the protection system tubing and
piping must be fabricated from noncombustible materials
suitable for prevailing hazards and environmental conditions.
The protective gas supply must originate from a dedicated
instrument quality compressed air header (1/2" pipe or
larger), no farther than twenty (20) feet from the protection
system. Local compressors and gas cylinders should not be
used before consulting with Fuchs.
The protective gas supply to the protection system must be
equipped with a tamper-proof regulator set at 5 psi maximum.
Exception:
If the protected enclosure(s) is equipped with an
EPV-3 Enclosure Protection Vent, the protective gas supply
to the protection system must not exceed 120 psi maximum,
5 psi minimum.
Pneumatic Connection Requirements
ALL FITTINGS MAY BE CUSTOMER OR FACTORY FURNISHED
1.
For system supply, one (1) SC-6 3/8" Male Straight
Connector or one (1) NC-6 3/8" Male Elbow Connector
or equivalent fitting per system.
NOTE: Above fitting is required only if protection
system is furnished with an optional In Line Filter Kit
(Model ILFK) accessory.
One (1) Similar fitting which will connect the inert gas
supply tubing to the inert gas supply header connection
point and one (1) lot of 3/8" O.D., .035" wall thickness,
welded or seamless stainless steel tubing.
2.
For enclosure supply, one (1) EFC-6 3/8" Flush
Connector, or one (1) EBC-6 3/8" Feed-Through
Connector or equivalent fitting per system.
3.
For enclosure reference, one (1) EFC-4 1/4" Flush
Connector, or one (1) EBC-4 1/4" Feed-Through
Connector or equivalent fitting per system.
4.
One (1) lot of 1/4" & 3/8" O.D., .035" wall thickness,
welded or seamless stainless steel tubing.
5.
For multiple enclosure connections, two (2) EPC-13
1.25" Pipe Mounting Hubs or equivalent and 1.25" 150#
rated pipe couplings & unions per interconnection.
One (1) lot 150# rating 1.25" galvanized or aluminum
pipe and fittings, fully reamed and unrestricted.
In addition to item numbers 1, 4 and 5 above, the
following fittings are required for all PM configurations.
1.
For system supply on PM configurations, one (1)
additional EBC-6 or equivalent 3/8" Through Bulkhead
Fitting per system is required.
2.
For atmospheric reference, one (1) PRB-4 or equivalent
1/4" female bulkhead fitting and stainless steel sintered
element is required.
PM Pneumatic Connection Requirements
SYSTEM SUPPLY FITTINGS
SC-6
NC-6
ENCLOSURE SUPPLY & REFERENCE FITTINGS
EBC-4 & EBC-6
EFC-4 & EFC-6
EPC-13
SYSTEM ATMOSPHERIC REFERENCE FITTING
PRB-4
MULTIPLE ENCLOSURE CONNECTION FITTING