Getting Started
Establishing Connection Sizes, Lengths & Bends
TYPICAL SINGLE PROTECTED ENCLOSURE CONNECTIONS
PROTECTED
ENCLOSURE
C
B
ENCLOSURE PROTECTION VENT
(Optional)
E
SUPPLY
REFERENCE
1/2"
PROTECTIVE
GAS SUPPLY
HEADER
ENCLOSURE
PROTECTION
SYSTEM
Maximum Tubing / Pipe Length and
Maximum Number of Bends / Elbows
3/8" O.D. Tubing
Fully Reamed
20 Feet
10 Bends
3/8" O.D. Tubing
Fully Reamed
Description
*Tubing or Pipe Diameter
Enclosure
Supply
System
Supply Tubing
Enclosure
Reference
1/4" O.D. Tubing
Fully Reamed
5 Feet
5 Bends
20 Feet
10 Bends
Multi - Enclosure
Connections
1" I.D. Pipe
Fully Reamed
10 Feet
5 Elbows
Optional Remote
Venting
1" I.D. Pipe
Fully Reamed
30 Feet
5 Elbows
A
B
E
D
C
ENCLOSURE
PROTECTION
SYSTEM
PROTECTED
ENCLOSURE
PROTECTED
ENCLOSURE
D
SUPPLY
REFERENCE
B
TYPICAL MULTIPLE PROTECTED ENCLOSURE CONNECTIONS
1/2"
PROTECTIVE
GAS SUPPLY
HEADER
A
A
D
C
HELPFUL HINTS
To ensure adequate protective gas flow to the protected enclosure(s), all piping and tubing must be fully reamed.
Precautions must be taken to prevent crimping and other damage to protective gas piping and tubing.
When protecting multiple enclosures with a single enclosure protection system, the enclosures must be
connected in series from the smallest to the largest to ensure adequate protective gas flow.
PROTECTED
ENCLOSURE
nnoott
*NOTE: Tube and pipe sizes are trade sizes and are not equal in inside
diameter. DO NO substitute tube for pipe with same trade size.