Page 32
Code
Fault Message
Possible reasons
Remedy
F032
Fan Motor2 Fault
1. Motor is in locked-rotor
state.
2.The wire connection be-
tween fan controller and fan
motor is in poor contact.
1.Change a new fan motor
2.Check the wire connection
and make sure they are in
good contact.
F01
Drv1 MOP alarm
MOP drive alarm
Recovery after the 150s
F02
Inverter offline
Frequency conversion board
and main board communica-
tion failure.
Check the communication
connection.
F03
IPM protection
IPM modular protection
Recovery after the 150s
F04
Comp. Driver Failure
Lack of phase, step or drive
hardware damage.
Check the measuring voltage
and frequency conversion
board hardware.
F05
DC Fan Fault
Motor current feedback open
circuit or short circuit.
Check whether current re-
turn wires connected motor.
F06
IPM Overcurrent
IPM Input current is large.
Check and adjust the current
measurement.
F07
Inv. DC Overvoltage
DC bus voltage>Dc bus
over-voltage protection
value.
Check the input voltage
measurement.
F08
Inv. DC Lessvoltage
DC bus voltage<Dc bus
over-voltage protection
value.
Check the input voltage
measurement.
F09
Inv. Input Lessvolt.
The input voltage is low,
causing the input current is
high.
Check the input voltage
measurement.
F10
Inv. Input Overvolt.
The input voltage is too high,
more than outage protection
current RMS.
Check the input voltage
measurement.
F11
Inv. Sampling Volt.
The input voltage sampling
fault.
Check and adjust the current
measurement
F12
Comm. Err DSP-PFC
DSP and PFC connect fault.
Check the communication
connection.
F26
Input Over Cur.
The equipment load is too
large.
F27
PFC fault
The PFC circuit protection.
Check the PFC switch tube
short circuit or not.
F15
IPM Overheating
The IPM module is overheat
Check and adjust the current
measurement.
F16
Weak Magnetic Warn
Compressor magnetic force
is not enough.
Maintenance & Troubleshooting
System Protections / Error Codes (Continued)