Connecting the Heat Pump to Automation
To connect the external control cable plug to the motherboard:
1. Run a two-conductor cable from the heat pump external control to the low voltage raceway to the
motherboard in the Pentair Automation control centre.
2. Strip the conductors 7mm. Insert the wires into the GAS HEATER two-screw terminals (J19) on the
motherboard.
3. At the heat pump, connect the wires to “remote on/off” on the terminal block.
4. Do NOT disconnect or wire around the thermostat, pressure switch, high limit switch, or other
safety devices.
5. Turn the thermostat for the selected setting to maximum.
Pool/Spa Heating Combinations (Recommended Configurations)
Heat Sources
Connections
EasyTouch Configuration
Heat Pump Only
Connect heat pump to 2-wire ter-
minal marked “Gas Heater” (J19).
Menu>Heat Menu>Pool Temp/
SRC>Heater
Menu>Heat Menu>Spa Temp/
SRC>Heater
Heat Pump + Gas Heater
Connect gas heater to 2-wire ter-
minal marked “Gas Heater” (J19).
Connect heat pump to relay con-
nected to “Solar” terminal.
Menu>Settings>Solar>Enable = Yes
Menu>Settings>Solar>Solar is Heat
Pump = Yes
Menu>Heat Menu>Pool Temp/
SRC>Heat Pump
Menu>Heat Menu>Spa Temp/
SRC>Heater
Heat Pump + Solar
Connect heat pump to 2-wire ter-
minal marked “Gas Heater” (J19).
Connect solar valve actuator to
VLVA (single pump system) or con-
nect solar booster pump electrical
outlet relay to “Solar” terminal
(separate solar pump system).
Menu>Settings>Solar>Enable = Yes
Menu>Heat Menu>Pool Temp/
SRC>Solar (or solar preferred).
Menu>Heat Menu>Spa Temp/
SRC>Heater
Menu>Settings>Solar>Solar is Heat
Pump = NO
Automation Connection