![Pentair raychem ngc-30/uit2 Programming Manual Download Page 76](http://html1.mh-extra.com/html/pentair/raychem-ngc-30-uit2/raychem-ngc-30-uit2_programming-manual_1524541076.webp)
76 / 84
industrial heat tracing solutions
EN-RaychemNGC30UIT2Programming-AR-H58186 02/16
Setup | Temp Screen
Setpoint Deadband High Temp
Alarm
Low Temp
Alarm
High Limit
Cut-Out
Enable
High Limit
Cut-Out
Temp
Low Limit
Cut-Out
Enable
Low Limit
Cut-Out
Temp
Low Limit
Cut-Out
Deadband
Low Limit
Cut-Out
Latching
Temperature
Alarm Filter
Default =
50ºF
Default
= 5ºF
Default =
300ºF
Default =
10ºF
Default =
Disable
Default =
900ºF
Default =
Disable
Default =
-94ºF
Default
= 5ºF
Default =
NonLatching
Default =
900 Seconds
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
Device
Device Type
Switch Setting
Device Address
NGC-30-CRM/CRMS
Relay Output / RTD
1 – 99
1 – 99
RMM2
RTD
0 – F
32 – 47
PLI
RTD
1 – 99
1 – 99
RMM-DI
Digital Input
0-F(High), 0-F(Low)
1-247
RMC
Digital Input / Relay Output
1-255
1-247
Setup | G.F. Screen
Setup | Current Screen
Setup | Voltage
G.F.
Current
Alarm
G.F.
Current
Trip
G.F. Trip
(Enable/
Disable
Low
Current
Alarm
High
Current
Alarm
Power
Limit
Low
Voltage
Alarm
High
Voltage
Alarm
Default =
20mA
Default =
30mA
Default =
Enable
Default =
5.0A
Default =
30.0A
Default
= 100
Default =
90V
Default =
270V
NGC-UIT2 Circuit Setup Worksheet
(page 2 of 4)