30 / 84
industrial heat tracing solutions
EN-RaychemNGC30UIT2Programming-AR-H58186 02/16
3.3.3 setuP | CirCuit WindoW
The Setup | Circuit window is the first window of the Setup sequence.
Fig. 3.8 Setup | Circuit window
Circuit entry Field
The Circuit # is assigned when setting up a Circuit in the Raychem NGC-30 program. It is the
primary reference for all windows. Once a Circuit is added, you cannot change its Circuit number;
however you can delete the Circuit (except for Circuit 1). This Setup|Circuit window is also where
you can select an existing Circuit.
enabled/disabled toggle Button
When
enabled
, the NGC-UIT2 monitors and generates Circuit alarms.
If a relay output has been assigned to the Circuit, the relay output turns on or off based upon
set-up parameters and RTD inputs, and the selected control mode.
When
disabled
, the NGC-UIT2 has disabled the Circuit, and does
not
generate alarms or
control the relay assigned to the Circuit. The relay remains in the off position. The Circuit is
grayed out in the main window to show it is
disabled
.
delete Button
Deletes the Circuit that is currently being displayed and removes it from the main window. Any
Circuit can be deleted EXCEPT for Circuit 1. The program asks for confirmation before deleting.
id entry Field
The Circuit ID is user-definable name tag. The default is “ID XXX” (where XXX is the Circuit
number).
Limit: 40 characters (character strings are truncated on the Main Window after 16
characters but displayed in full on Status and Setup win-dows)