![Pentair raychem ngc-30/uit2 Programming Manual Download Page 56](http://html1.mh-extra.com/html/pentair/raychem-ngc-30-uit2/raychem-ngc-30-uit2_programming-manual_1524541056.webp)
56 / 84
industrial heat tracing solutions
EN-RaychemNGC30UIT2Programming-AR-H58186 02/16
3.3.24 netWork | deViCes WindoW
This window summarizes the device addresses and resources (output devices/ relays and RTD
inputs) that have been found by the system and can be used for setup.
Fig. 3.34 Network |Devices window
update network action Button
Pressing this button starts a search/scan for all connected peripheral devices. When the scan is
completed, the window displays all devices and RTDs found connected to the NGC-UIT2.
imPortant:
If expected devices or RTDs are not discovered on the first scan, Update Network
may be pressed a second time. If a known device or RTD is not discovered, check for proper
connection to the RS-485 wiring, power at the peripheral device, and possible address conflicts (no
two peripheral devices can have the same address setting).
Use the Update Network button whenever a new device or RTD is added to the system.
To add a new device or RTD, make sure it:
1. Has a unique address
2. Has power
3. Is connected to the RS-485 wiring
Then push Update Network to add the device to the list.
imPortant:
Removal of Device - If you remove a device or RTD from the network, using the
Update Network button will not remove the device from memory. You must use the “Remove
Device” button found in the Network|Remove window.
The table below shows the available device addresses for Relay Outputs and RTDs. If module(s)
are installed either in the field or in the NGC-30 panel, they must NOT share the same address as
the NGC-30-CRM/CRMS.
table 3.8 available device addresses
device
device type
switch setting
device address
NGC-30-CRM/-CRMS
Relay Output/RTD
1–99
1–99
PLI
RTD
1–99
1–99
NGC-20
Relay Output/RTD
Via Software*
1-247
RMM-DI
Digital Input
1-247
1-247