65 / 84
industrial heat tracing solutions
EN-RaychemNGC30UIT2Programming-AR-H58186 02/16
rs-485 Field
Fig. 3.46 System |Comm window (RS-485 Field Configuration)
rtu Character timeout entry Field
This sets the time the NGC-UIT2 waits after last character is received before it determines that the
message has ended.
Range:
0–1000 milliseconds
Default: 25
receive message timeout entry Field
The received message timeout is used to extend the previously computed message timeout which
is computed automatically by the NGC-UIT2. This timeout is mainly used for extending message
timeouts in modems etc.
Range:
0–1000 milliseconds
Default: 0
transmit delay entry Field
This sets the time the NGC-UIT2 will wait after it receives a message before it replies.
Range:
0–5000 milliseconds
Default: 0
Baud rate entry List
Allows you to select the baud rate of the external communication port.
Selection:
2400, 4800, 9600, 19200, 38400, 57600
Default: 9600
stop Bits
Allows you to select the number of stop bits used.
Range:
1–2
Default: 2
Parity
Allows you to select what type of parity will be used.
Selection:
None, Odd, Even
Default: None