2.4 startinG the nGC-30
2.4.1 system reQuirements
The minimum configuration to use the Raychem NGC-30 software is:
• Raychem NGC-UIT2 hardware
• At least one of the following:
– NGC-30-CRM/-CRMS
– RMM2 Remote Monitoring Module
– RMC Module
– NGC-20 Controller
Maximum optional equipment configuration:
• Up to 52 Heat Trace Controller Boards (total count in any combination)
– NGC-30-CRM
– NGC-30-CRMS
• Up to 16 RMM2 modules (8 channel RTD multiplexing hubs)
• Up to 4 PLI modules (127 RTDs if SES/SPC transmitters are used, or 255 RTDs if 700-TT
transmitters are used)
• Up to 247 NGC-20 controllers
• Up to 247 RMM-DI modules
Total combination of output devices including NGC-30-CRM/-CRMS, NGC-20 and RMC DO cannot
exceed 260 circuits.
2.4.2 initiaL setuP
The Raychem NGC-30 software is designed to run only on the NGC-UIT2 hardware platform.
Prior to shipment, the Raychem NGC-30 software is installed into a nonvolatile area of the NGC-
UIT2 memory. During the initial power-up, you will see a blue background “splash” window for
approximately 30 seconds as the system software is loaded and initializes.