ADDITIONAL INFORMATION
RS-485 COMMUNICATIONS
RS-485 is a US-based telecommunications standard for binary
serial communications between devices. It is the protocol, or
set of specifications, that needs to be followed to allow devices
that implement the standard to speak to each other.
A fully compliant RS-485 port is included in the Pentair Pentek
Intellidrive® Constant Pressure Pump Controller system to
permit serial connections among more than two devices on
an RS-485 compliant network. Figure 19 shows two-wire
connection to the Intellidrive.
LIGHTNING/SURGE PROTECTION
Lightning arrestors or other surge suppressing devices
can be used with this product. MOV (Metal Oxide Varistor),
SOV (Silicon Oxide Varistor).
RETROFIT APPLICATIONS
When retrofitting an installation, most of the preceding text can
be applied. As a convenience, the recommended Service Factor
Amps for non-Pentek motors is provided in Table 7.
Always verify Service Factor Amp values from current
manufacturer literature.
Motor Type
HP
Service Factor Rating,
in Amps
CentriPro¹
Franklin²
2-Wire
1/2
4.7
N/A
3/4
6.4
1
9.1
1-1/2
11.0
CS/CR 3-Wire
1/2
4.9
4.3
3/4
6.3
5.7
1
7.2
7.1
1-1/2
11.1
11.5
2
12.2
13.2
3-Phase
1/2
2.9
2.9
3/4
3.9
3.8
1
4.7
4.7
1-1/2
6.1
5.9
2
7.6
8.1
3
10.1
10.9
5
17.5
17.8
¹ CentriPro SFA data was taken from the March 2012 BMAID manual on 4/2012.
² Franklin Electric SFA data was taken from the 7/2011 Franklin Electric AIM manual on 4/2012.
NOTE: The Pentek Intellidrive will not operate Franklin Electric 2-wire motors.
Table 7 - Service Factor Amps @ 230V
INTELLIDRIVE RESET PROCEDURE
Follow this keypress sequence to test the Intellidrive (Figure 20).
NOTE:
In a domestic environment, this product may cause radio interference which may
require supplementary mitigation measures.
7064 0616
Press Password
button
Press Main Menu
button
Press up or down arrow
until Reset appears
Enter Passwword
(Default is 7777)
Press Enter
Press Enter
Press Enter to Edit
Change “No” to “Yes”
Confirm Reset
Figure 20 - Keypress Sequence For Testing
6544 0412
01+ 01- I1+ I1- I2+ I2- V+ V- AI+ AI- P N SD CARD
Figure 19 - Example RS-485 Connection