10
PN957 (25-06-20)
INITIAL STARTUP
Ensure that the cover is installed before operating the Pentair
Pentek Intellidrive® Constant Pressure Pump Controller.
Most installations will only require the initial startup settings.
However, the installer may need to set additional parameters.
Information about accessing all parameters, explanations of their
functions, and procedures for changing parameter values, will be
found later in this section.
1. Program the Intellidrive: Apply power to the device. Setup
Guide will appear in the display. Follow keypress sequence
shown in Figure 10.
NOTE:
If Setup Guide does not appear, refer to Intellidrive Reset
Procedure (Figure 20).
2.
Select 80 Hz Operation, if necessary (See 60 Hz to 80 Hz
Operation for more information):
Press MAIN MENU button.
Follow the keypress sequence shown in Figure 11.
3. Pump out well, if necessary. Direct discharge to appropriate
location not connected to system and press Pump Out.
The pump will run at 45 Hz. Adjust frequency as appropriate:
Press ENTER
Change frequency value. Above ground pumps should run at
60 Hz for this step (until pump is primed). Then adjust frequency
as necessary.
Press ENTER again.
INITIAL SETUP
Motor Type
Part Number
Rating @ 230V
Service Factor
Amps
HP
2-Wire
P42B0005A2-01
1/2
4.7
P42B0007A2-01
3/4
6.2
P42B0010A2-01
1
8.1
P42B0015A2-01
1-1/2
10.4
P42B0005A2-02
1/2
5.1
P42B0007A2-02
3/4
6.1
P42B0010A2-02
1
8.0
P42B0015A2-02
1 1/2
10.6
P42B0005A2
1/2
4.7
P42B0007A2
3/4
6.4
P42B0010A2
1
9.1
P42B0015A2
1-1/2
11.0
CS/CR 3-Wire
P43B0005A2-01
1/2
4.8
P43B0007A2-01
3/4
6.0
P43B0010A2-01
1
7.3
P43B0015A2-01
1-1/2
10.9
P43B0005A2-02
1/2
4.5
P43B0007A2-02
3/4
5.7
P43B0010A2-02
1
6.8
P43B0015A2-02
1 1/2
10.7
P43B0005A2
1/2
4.9
P43B0007A2
3/4
6.3
P43B0010A2
1
7.2
P43B0015A2
1-1/2
11.1
P43B0020A2
2
12.2
3-Phase
P43B0005A3
1/2
2.9
P43B0007A3
3/4
3.9
P43B0010A3
1
4.7
P43B0015A3
1-1/2
6.1
P43B0020A3
2
7.6
P43B0030A3
3
10.1
P43B0050A3
5
17.5
Table 2 - Pentek Motor Service Factor Amps
Press Enter
Press Enter
Press Enter
Press Enter
6566 0512
Apply 230V to Drive
Set Time
Set Date
Setup Complete
1 Phase
Connection Type
(2 Wire or 3 Wire)
3 Phase
Motor Type
Subm or Above Gnd
Enter Service Factor Amps
Enter Motor Phase
(1 Phase or 3 Phase)
Press Enter
Figure 10 - Intellidrive Setup Guide
6570 0512_EN
Use arrows to
scroll to Motor
Press Enter
Use arrows to
select 80 Hz
Press Enter to save
Press MAIN MENU button
Press Enter
Use arrows to select
Max Frequency
Figure 11 - Select 80 Hz
(3-phase submersible operation only)