14
PN957 (25-06-20)
PROGRAMMING
Menu
Settings
Parameter
Unit of Measure
Value
Description
Default
Min.
Max.
Ex Runtime
Excessive Runtime Detection
_
Disabled
Disabled
Enabled Enables or disables Excessive Runtime Detection.
Excessive Runtime Hours
Hours
24
1
100
Number of hours Intellidrive can run before it faults on Excessive
Runtime.
Dry Run
Auto Restart Delay
Minutes
10 Min
3 Min
60 Min
Time Pentair Pentek Intellidrive® Constant Pressure Pump
Controller waits to restart pump when Dry Run is detected.
Number of Resets
–
3
0
5
Number of tries Intellidrive attempts to restart pump when Dry
Run condition is detected.
Detection Time
M:SS
15 Sec
5 Sec
10 Min Time the Intellidrive takes to recognize Dry Run condition.
Sensitivity
PSI
10
0
300
Pressure value that Dry Run condition is detected at. Dry Run
fault will occur if this pressure cannot be met within Detection
Time window. Lower pressure = less sensitivity.
Fill Time
M:SS
1 M
15 S
10 M
Time allowed to fill (prime) pipes during Auto Line Fill process.
Relates to Dry Run Sensitivity value. (Time starts after 55 Hz is
reached).
I/O
Digital Input 1
–
Unused
–
–
Selects operation of Intellidrive when terminal I1 or I2 is used.
Select between Unused, Run Enabled, Ext Fault, and Setpoint.
The Intellidrive will respond to selected command when voltage is
present at I1 or I2 terminal.
Digital Input 2
–
Unused
–
–
Relay Output
–
Unused
–
–
Selects the operation of Intellidrive when terminal O1 is used.
Select between Unused, Run, and Fault. The Intellidrive closes
the Relay when Run or Fault is selected.
Over Press
Over Pressure
PSI
80 PSI
15 PSI
97 PSI
Sets Over Pressure Warning value. Change if higher than 80 PSI
system pressure is needed.
No Ground
No Ground Detection
–
Enabled
Disabled
Enabled
Selects whether Ground Detection parameter is Enabled or
Disabled. If Disabled is selected, it will revert back to Enabled
after 72 hours. Warning LED will flash entire time it is Disabled.
Reset
Factory Reset
–
No
No
Yes
Resets all parameters to factory defaults. Displays Setup Guide
after it is complete. Software version displayed here. Does not
clear fault log.
SW Update
Software Update
–
Disabled
Disabled
Enabled Used to update software, if necessary.
Table 5, Continued - Main Menu and Parameters