Pentair Hydromatic Installation And Service Manual Download Page 2

2

personnel capable of using 

reasonable engineering principles 

for the installation and operation 

of the system.

Excavation 

Instructions

Excavation location shall be 

made according to local codes 

and regulations. Check with 

local utility companies for 

 

the location of underground 

utilities prior to excavation. 

Care should be taken to avoid 

buried utility lines, piping, and 

other buried structures and 

foundations. Failure to follow 

these instructions may result  

in serious personal injury or 

death.
Excavation for Basin Systems

Effect appropriate excavation 

based on size of the basin, desired 

entrance point of the influent line, 

and entrance of power connection.

General 

Information

Thank you for purchasing your 

Low Pressure Sewer Basin 

System.
Before Installation:

This manual contains important 

information for the safe use of 

this product. Read this manual 

completely and follow the 

instructions carefully. Reasonable 

care and safe methods relating 

to the installation and operation 

of this product should be 

practiced. Check local codes and 

requirements before installation.

Risk of electrical shock or 

electrocution. May result 

in serious injury or death or  

fire hazard. Installer must 

disconnect all electrical sources 

prior to installation. Only 

qualified personnel may install 

this system. NFPA 70/National 

Electric Code (NEC) or local 

codes must be followed. System 

must be properly grounded 

according to NEC.

Biohazard risk. Once the 

wastewater source has been 

connected to system, biohazard 

risk exists. Installer(s) and/

or service personnel must use 

proper Personal Protective 

Equipment and follow handling 

procedures per OSHA 29 CFR 

1910.1030 when handling 

equipment after wastewater 

source has been connected to 

the system.

Risk of fire or explosion. Do 

not smoke or use open flames 

in or around this system. This 

system is not intended for use in 

hazardous locations per NFPA 

70 National Electric Code. 

Consult factory for optional 

equipment rated for this use.

Cutting risk. Risk of serious 

cutting or amputation exists. 

Disconnect all power sources 

prior to servicing pump or 

grinding mechanism. Pump may 

start without warning. Grinding 

mechanism is extremely sharp. 

Use caution when handling 

grinder mechanism.
CALIFORNIA PROPOSITION 

65 WARNING:

  This product and 

related accessories contain 

chemicals known to the State of 

California to cause cancer, birth 

defects or other reproductive 

harm.
DO NOT THROW AWAY OR 

LOSE THIS MANUAL. Keep 

it in a safe place so that you may 

refer to it often for the continued 

safe operation of the product.

Installation Skill 

Requirements

The installation of a basin system  

is a specialized skill, which 

requires individuals with the basic 

understanding of excavating, pipe 

fitting, and electrical wiring. 
These instructions are meant 

only to be an installation guide; 

therefore, unusual installation 

conditions not covered in these 

instructions require experienced 

Summary of Contents for Hydromatic

Page 1: ...ovide this manual to the owner of the equip ment or to the responsible party who maintains the system COMPLETE GRINDER PACKAGE SYSTEM TH PRO SYSTEM INSTALLATION AND SERVICE MANUAL Item E 03 515 Part 5625 515 1 2012 Pentair Pump Group Inc 11 05 12 ...

Page 2: ...ust be followed System must be properly grounded according to NEC Biohazard risk Once the wastewater source has been connected to system biohazard risk exists Installer s and or service personnel must use proper Personal Protective Equipment and follow handling procedures per OSHA 29 CFR 1910 1030 when handling equipment after wastewater source has been connected to the system Risk of fire or expl...

Page 3: ...drilled hole PIPE SIZE HOLE SAW DIAMETER 3 4 4 5 6 7 Contact the factory for availability of proper size hole saw if necessary 6 pipe size requires use of a fiberglass basin Failure to use a properly piloted hole saw may result in damage to basin which may result in structural failure or serious leaks Step 2 Lubricate inside lip of inlet grommet with pipe soap Clean outer end of influent pipe and ...

Page 4: ...ing live electrical connections Step 1 Obtain proper backfill material The backfill material provides as much as 90 of the basin s support under certain stress conditions The installer must be positive that correct bed and backfill materials are used per instructions as follows A Gravel clean and free flowing with particle size not less than 1 8 or more than 3 4 in diameter Use this description wh...

Page 5: ...g Grinding mechanism is extremely sharp Use caution when handling the grinder mechanism Risk of fire or explosion Do not smoke or use open flames in or around this system This system is not intended for use in hazardous locations per NFPA 70NationalElectricCode Consult factory for optional equipment rated for this use Unpacking Pump Remove pump from carton When unpacking unit check for concealed d...

Page 6: ...int at which the electrical conduit will enter the basin and using a 3 diameter properly maintained piloted hole saw drill a hole through the basin wall If using a fiberglass basin clean the edges of the hole and apply a sealant coating to the cut section to prevent fiberglass deterioration Insert the inlet grommet into the drilled hole Failure to use a properly piloted hole saw may result in dama...

Page 7: ... breaker Step 4 Start the pump by pushing the Push to run push button inside the control panel Step 5 Check the pump amperage with clamp on ammeter on black pump lead Readings higher than nameplate indicate clogged pump miswiring or improper voltage If basin is not being pumped down and amperage readings are considerably lower than nameplate then the pump is air locked 1 Cutters may be clogged Amp...

Page 8: ...ally suspend the Off float the pump should stop running If this procedure does not cause the pump to operate as described either replace the float s or replace the alternator relay if the system is duplex Circuit breaker trips when pump tries to start 1 Short circuit in pump motor 2 Water may have entered the motor housing through either worn out mechanical seals or O rings 3 Start component s fai...

Page 9: ...03 1 Stand for HPD200 Positive Displacement Pump 1 27078B005 Stand for HGRS200 Centrifugal Pump 1 3 12870 015 1 Junction Box NEMA 6 2 NPT 1 4 14595 320 1 Float control pump 20 cord 1 5 21813A322 Float control alarm 20 cord 1 6 22470B005 Float control bracket 1 7 23901D303 Basin 24 x 48 Fiberglass 1 23901D301 Basin 24 x 60 Fiberglass 1 23901D304 Basin 24 x 72 Fiberglass 1 23901D306 Basin 24 x 84 Fi...

Page 10: ...THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 11: ...THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 12: ...ting from failure to properly install operate or maintain the unit in accordance with the printed instructions provided b to failures resulting from abuse accident or negligence c to normal maintenance services and parts used in connection with such service d to units that are not installed in accordance with applicable local codes ordinances and good trade practices e if the unit is moved from it...