8
•
FLECK
7000XTR Service Manual
MASTER PROGRAMMING MODE
When the Master Programming Mode is entered, parameters
can be set to make the timer function as needed.
CAUTION
Before entering Master Programming, please
contact your local professional water dealer.
NOTE: Depending on current option settings, some displays
cannot be viewed or set.
Entering Master Programming Mode:
1. Press and hold the Shift and Up buttons for 5 seconds.
OR
2. Set the time of day display to 12:01 PM or 12:01HR (See
the User Programming section to learn how to set Time of
Day). Then go to the main display screen, press the Up and
Down buttons at the same time for 5 seconds.
Exiting Master Programming Mode:
1. Press the Extra Cycle button once per display until all
are viewed. Master Programming Mode is exited and the
normal display screen appears.
2. To exit the Master Programming Mode without saving,
press the Diagnostic button.
NOTE: If no keypad activity is made for 5 minutes while in
the Master Programming Mode, or if there is a power
failure, no changes will be made, and the unit will go
back to the main display screen.
Resets:
Soft Reset: Press and hold the Up and Down buttons for 25
seconds until 12:00PM (or 12:00HR) appears. This resets all
parameters except for the flow meter totalizer volume.
Master Reset: Hold the Extra Cycle button while powering up
the unit. This resets all of the parameters in the unit. Check
and verify the choices selected in Master Programming Mode.
1. System Type
This program step selects the system type.
• Press the Up or Down buttons to adjust this value.
• Press the Extra Cycle button.
2. Valve Type
This program step selects the valve type.
• Press the Up or Down buttons to adjust this value.
• Press the Extra Cycle button.
3. Regenerant Flow
This program step selects how the regenerant flows through
the tank (must match cam). The selections available will vary
depending on the previously chosen valve model.
• Press the Up or Down buttons to adjust this value.
• Press the Extra Cycle button.
4. Display Format
This program step selects the display format.
• Press the Up or Down buttons to adjust this value.
• Press the Extra Cycle button.
5. Unit Capacity
This program step selects the timer’s total capacity of
hardness that can be removed.
• Press the Shift button to select the digit you want to modify.
• Press the Up or Down buttons to adjust this value.
• Press the Extra Cycle button.
6. Feed Water (Hardness)
This program step is used to set the feed water hardness. The
system will automatically calculate volume remaining based
on the unit capacity, capacity safety factor, and feed water
hardness entered.
• Press the Shift button to select the digit you want to modify.
• Press the Up or Down buttons to adjust this value.
• Press the Extra Cycle button.
NOTE: Feed Water Hardness will not be shown in Volume
Override or Time Clock system types.
7. Capacity Safety Factor
This program step is used to set the reserve capacity of the unit.
This is a percentage by which the unit’s capacity is reduced.
• Press the Shift button to select the digit you want to modify.
• Press the Up or Down buttons to adjust this value.
• Press the Extra Cycle button.
8. Volume Override
This program step is used to set the volume override of the unit.
• Press the Shift button to select the digit you want to modify.
• Press the Up or Down buttons to adjust this value.
• Press the Extra Cycle button.
Summary of Contents for FLECK 7000XTR
Page 1: ...www pentairaqua com FLECK 7000XTR SERVICE MANUAL...
Page 7: ...FLECK 7000XTR Service Manual 7 MASTER PROGRAMMING MODE FLOW CHART CONTINUED...
Page 13: ...FLECK 7000XTR Service Manual 13 CONTROL VALVE ASSEMBLY 61500 7000EXP REV C...
Page 23: ...FLECK 7000XTR Service Manual 23 INJECTOR FLOW DATA TR18755 REV B...