MASTER PROGRAMMING MODE

When the Master Programming Mode is entered, parameters 

can be set to make the timer function as needed. 

CAUTION

 Before entering Master Programming, please 

contact your local professional water dealer.

NOTE:   Depending on current option settings, some displays 

cannot be viewed or set. 

Entering Master Programming Mode:

1.  Press and hold the Shift and Up buttons for 5 seconds. 
OR
2.  Set the time of day display to 12:01 PM or 12:01HR (See 

the User Programming section to learn how to set Time of 

Day). Then go to the main display screen, press the Up and 

Down buttons at the same time for 5 seconds. 

Exiting Master Programming Mode:

1.  Press the Extra Cycle button once per display until all 

are viewed. Master Programming Mode is exited and the 

normal display screen appears.

2.  To exit the Master Programming Mode without saving, 

press the Diagnostic button.

NOTE:    If no keypad activity is made for 5 minutes while in 

the Master Programming Mode, or if there is a power 

failure, no changes will be made, and the unit will go 

back to the main display screen.

Resets:

Soft Reset: Press and hold the Up and Down buttons for 25 

seconds until 12:00PM (or 12:00HR) appears. This resets all 

parameters except for the flow meter totalizer volume.
Master Reset: Hold the Extra Cycle button while powering up 

the unit. This resets all of the parameters in the unit. Check 

and verify the choices selected in Master Programming Mode.

1. System Type

This program step selects the system type.

•  Press the Up or Down buttons to adjust this value.
•  Press the Extra Cycle button.

2. Valve Type

This program step selects the valve type.

•  Press the Up or Down buttons to adjust this value.
•  Press the Extra Cycle button.

3. Regenerant Flow

This program step selects how the regenerant flows through 

the tank (must match cam). The selections available will vary 

depending on the previously chosen valve model.

•  Press the Up or Down buttons to adjust this value.
•  Press the Extra Cycle button.

4. Display Format

This program step selects the display format.

•  Press the Up or Down buttons to adjust this value.
•  Press the Extra Cycle button.

5. Unit Capacity

This program step selects the timer’s total capacity of 

hardness that can be removed.

•  Press the Shift button to select the digit you want to modify.
•  Press the Up or Down buttons to adjust this value.
•  Press the Extra Cycle button.

6. Feed Water (Hardness)

This program step is used to set the feed water hardness. The 

system will automatically calculate volume remaining based 

on the unit capacity, capacity safety factor, and feed water 

hardness entered.

•  Press the Shift button to select the digit you want to modify.
•  Press the Up or Down buttons to adjust this value.
•  Press the Extra Cycle button.

NOTE:   Feed Water Hardness will not be shown in Volume 

Override or Time Clock system types.

7. Capacity Safety Factor

This program step is used to set the reserve capacity of the unit. 

This is a percentage by which the unit’s capacity is reduced.

•  Press the Shift button to select the digit you want to modify.
•  Press the Up or Down buttons to adjust this value.
•  Press the Extra Cycle button.

8. Volume Override

This program step is used to set the volume override of the unit.

•  Press the Shift button to select the digit you want to modify.
•  Press the Up or Down buttons to adjust this value.
•  Press the Extra Cycle button.

Summary of Contents for FLECK 7000XTR

Page 1: ...www pentairaqua com FLECK 7000XTR SERVICE MANUAL...

Page 2: ...be installed by a plumbing professional This unit is designed to be installed on potable water systems only This product must be installed in compliance with all state and municipal plumbing and elect...

Page 3: ...ss __________Grains French Degrees German Degrees PPM 7 Capacity Safety Factor A Zero B __________ 8 Volume Override __________ Gallons or M3 9 Regeneration Day Override A Off B Every__________Days 10...

Page 4: ...to local plumbing codes 3 Cut the 1 05 inch 2 6 cm distributor tube flush with the top of the tank A Deburr the outside of the tube B after cutting Lubricate the o ring C with non petroleum based grea...

Page 5: ...eration time has been reached Meter Delayed Weekly Reserve A Volume remaining has been depleted to the weekly variable reserve volume and B the regeneration time has been reached Volume Override Immed...

Page 6: ...ay Regeneration Day Override Feature If the Day Override option is turned on and the valve reaches the set Regeneration Day Override value the Regeneration Cycle starts at the programmed regeneration...

Page 7: ...FLECK 7000XTR Service Manual 7 MASTER PROGRAMMING MODE FLOW CHART CONTINUED...

Page 8: ...tra Cycle button 2 Valve Type This program step selects the valve type Press the Up or Down buttons to adjust this value Press the Extra Cycle button 3 Regenerant Flow This program step selects how th...

Page 9: ...y Output Window Start End Time Setting This option setting consists of two displays The first display sets the turn on time of the output referenced to the start of the first regeneration cycle The se...

Page 10: ...types 3 Set Regeneration Day Override To turn on and set the days press the Down button Press the Shift Up and Down buttons to move the cursor and change the value of the numbers Press the Extra Cycl...

Page 11: ...the Extra Cycle button 2 Peak Flow Rate This program step displays the peak flow rate 1 minute average since the last regeneration Press the Extra Cycle button 3 Totalizer This program step displays t...

Page 12: ...ar Main 7 1 40704 Cam Brine Downflow 8 1 40979 Plate Lower Support 9 1 61635 01 Cover Assy 7000 II Black 1 61634 01 Cover Assy 7000 II Gray 10 1 40980 Backplate 7000 11 4 13602 Screw Phil Rd Hd 6 32 x...

Page 13: ...FLECK 7000XTR Service Manual 13 CONTROL VALVE ASSEMBLY 61500 7000EXP REV C...

Page 14: ...C Assemblies DLFC Size GPM 61455 00 3 4 inch Blank 61455 17 3 4 inch 1 7 61455 20 3 4 inch 2 0 61455 24 3 4 inch 2 4 61455 30 3 4 inch 3 0 61455 35 3 4 inch 3 5 61455 40 3 4 inch 4 0 61455 45 3 4 inch...

Page 15: ...ch BSP w O ring 3 2 41242 01 Connector Assy 1 inch 1 4 inch Sweat w O ring 41243 01 Connector Assy 1 1 4 inch 1 1 2 inch Sweat w O ring 4 2 40576 Clip H Plastic 7000 5 1 40951 O ring 220 Not Shown 1 6...

Page 16: ...LECK 7000XTR Service Manual 2310 SAFETY BRINE VALVE Item No QTY Part No Description 1 1 60014 Safety Brine Valve Assy 2310 2 1 60068 30 Float Assy 2310 w 30 inch Rod 3 1 60002 34 Air Check 500 42112 R...

Page 17: ...Flashing blinking display Power outage has occurred Either wait 5 minutes for blinking to stop or press any key on the keypad Unit not responding after going into regeneration Verify the unit is confi...

Page 18: ...system Remove piston and clean control Loss of mineral through drain line Air in water system Assure that well system has proper air eliminator control Check for dry well condition Improperly sized dr...

Page 19: ...ts and reset reserve capacity to provide additional reserve Meter is not measuring flow On Mechanical Meter Check with meter checker kit If volume is not registering check the meter cap and impeller f...

Page 20: ...REV A 41121 REV A Backwash Position 40988 REV A 41121 REV A Brine Position 40988 REV A 41121 REV A Slow Rinse Position 40988 REV A 41121 REV A Second Backwash Position 40988 REV A 41121 REV A Rapid R...

Page 21: ...t board align notches on left side of board with flexible finger on power head Apply pressure to left while rotating the board back 42554 REV A 2 When all the way down snap the circuit board into plac...

Page 22: ...22 FLECK 7000XTR Service Manual DIMENSIONAL DRAWINGS 61500 7000XTR LNE REV A METER FLOW DATA TR18753 Softener TR18688 Filter 41140 02 REV A...

Page 23: ...FLECK 7000XTR Service Manual 23 INJECTOR FLOW DATA TR18755 REV B...

Page 24: ...emarks and logos are the property of their respective owners Because we are continuously improving our products and services Pentair reserves the right to change specifications without prior notice Pe...

Reviews: