Addendum e to InstructIon And operAtIng mAnuAl
7� INSTAllATION
iMpOrTAnT
The installation must be carried out in accordance
to the applicable standards IEC/EN 60079-14
and IEC/EN 60079-17 regarding the electrical
installations in Hazardous Areas (other than
mines) classified as Zones 1, 2 (gas) and
Zones 21, 22 (dust) following IEC/EN 60079-10-1
and IEC/EN 60079-10-2 and any other applicable
national standards and rules.
7.1 WOrking COndiTiOn
WArning
For the correct utilisation with respect to the
safety and the functionality of the enclosures
components, check the "temperature ambient
range" embossed on the nameplate.
7.1.1 Models and temperature
ICON-010, ICON-020 and ICON-030, ICON-040,
ICON-050:
• from -25°C to +60°C (from -13°F to +140°F)
iMpOrTAnT
When alternative entries according ISO 965 are
used, indication of the dimensions is imprinted on
the adaptor bush or directly on the housing when
ISO 965 entries are obtained by machining the
housing.
entry
npT size
Alternative
(Metric size iSO 965)
1
1”
M32x1�5
2
1-½”
M40x1�5
3
1”
M32x1�5
4 (optional)
¾”
M25x1�5
7.2 idenTifiCATiOn Of enTrieS
7.2.1 Base actuator
Electric actuators Series ICON 2000 are
equipped with 4 entries (3 are standard, the
fourth is supplied when requested)�
With reference to the attached picture, the
thread form/size for each entry is as follows:
7.3 eleCTriCAl COnneCTiOnS
The instructions of VCIOM-01232 main
Instruction and Operating Manual applies�
7.4 CABle COnneCTiOn
Sealing of cables entries must be carried out
in accordance with national standards or the
regulatory authorities that have certified the
extension with additional conduit entry�
Method of sealing and cable glands must be
approved and separately certified for use in
hazardous areas�
Two earth points of connection, one internal
and one external, are foreseen on the base
ICON 2000 units enclosure for the ground
cables connection�
iMpOrTAnT
To prevent any water infiltration through the line
cable conduits, be sure the cable glands used
have the minimum degree of protection required
by the plant and specified on the actuator label.
To guarantee that the weatherproof and
explosion-proof characteristics are respected,
screw the cable gland or the external ATEX
certified apparatus tightly (at least 5 turns) and
block them with a thread sealant�
iMpOrTAnT
The cables and cable glands MUST be selected
considering the maximum temperature of the
cable indicated on the label fixed to the base
ICON 2000 unit.
7.5 inSTAllATiOn in AMBienT WiTH
explOSiVe duSTS
Special attention must do to these following
points:
• Before the assembly the joint surfaces must
be greased with Aeroshell grease�
• The cable glands must have a protection
degree at minimum IP66 or IP68
(15 m depth / 90 hours) according to
IEC/EN 60529 standard�
• Periodically verify the quantity of dust
deposited on the enclosure and clean it in the
case the quantity becoming more than 5 mm�
Internal earth stud
External earth stud