View procedure
• Move the local selector to OFF and then
simultaneously press OPEN and STOP� Select
the language according to the instructions
(see “Entering the view mode”)� When the
message displayed is “VIEW MODE OK?”
press yES� Press NO to scroll the list of
available menus and press yES to select
maintenance menu�
• Press NO to scroll the list of routines and
press yES to select data logger�
• Press YES to view the MODE, the SAMPLING
time, the MEMORy mode, the start DATE and
the start TIME�
• Press YES to return data logger. Press NO
to exit�
• EVENT mode: the ICON 2000 detects the
type of received command (OPEN or CLOSE),
the source of the command (local controls,
remote controls, bus, etc�) and date and
time of command� up to 128 EVENTS can
be memorized� As the memory is full,
the logger stops to memorize events or
overwrites the previous data according to
the selected MEMORy MODE (“stop when
full” or “continuous”)� If “continuous” was
selected, as a new event is achieved the
oldest one is cancelled and the new one
becomes the latest� up to 50 cycles of full
memory overwriting are done, then the logger
stops� The START DATE and START TIME fix
date and time to start recording operation�
By a PDA or PC the collected data can be
viewed by a graph or event table� Parameter
“sampling time” is not used� The figure below
shows an example of report in EVENT mode�
Main supply voltage
Temperature of electronics
Motor temperature
The figure below shows a graph with sampling
time 2 secs in RECORDER mode�
The figure below shows a graph with sampling
time 1 sec in T-RECORDER mode after a
recording stop for OVER-TORQuE alarm:
1� Torque limit in OP reached
2� Curve selector:
- Torque
- Motor temperature
- Main voltage
Torque limit in CL is set to 90%, torque limit
in OP is set to 100%. Blue graph shows
Torque OP versus time, yellow grap shows
Torque CL versus time� The data remain in the
ICON 2000 v4 permanent memory untl a new
start of data logger is set�