![Pentair Biffi ICON 2000 Instructions And Operating Manual Download Page 19](http://html1.mh-extra.com/html/pentair/biffi-icon-2000/biffi-icon-2000_instructions-and-operating-manual_1524512019.webp)
19
4
6
1
3
2
5
Biffi
ICON 2000
InstructIon and operatIng manual
6� LOCAL CONTROLS
6.1 description of the local operator
interface
The following functions are available by the
ICON 2000 local operator interface:
numeric display
to indicate the present valve
position as a % of the opening.
Display resolution in function of the actuator
stroke turns:
- From 2.8 to 5.5 turns = 1%
- From 5.5 to 13.8 turns = 0.5%
- From 13.8 to 27.7 turns = 0.2%
- From 27.7 to 10,000 turns = 0.1%
3-position selector
to set the following
operation modes:
- LOCAL: for local control only
- Off: no control is active but the actuator is
still connected to the mains
- REMOTE: for remote control only
alphanumeric display:
during normal
operation the alphanumeric display shows the
present status (NORMAL, ESD ON, ALARM,
WARNING, INTERLOCK), the 3-position
selector status (LOCAL, Off, REMOTE) and the
actuator action (OPEN, OPENING, CLOSED,
CLOSING, STOP or
R% : xxx.x). If the local selector is in OFF or
REMOTE, pressing the yES push-button it is
possible to scroll the list of variables, alarms
and reports:
close/no
stop
open/yes
The ICON 2000 can be provided with a
radiofrequency wireless connection based on
a qualified
Bluetooth™
class 1 module� This
allows to establish a connection and exchange
data with a PDA or PC with built-in Bluetooth™
technology� The following tasks can be
wirelessly performed:
- View and change configuration
- Set maintenance function
- Read maintenance data
- Download new firmware to the ICON 2000
- The blue LED indicates that the
communication with a host device is
established
local controls:
OPEN/yES, CLOSE/NO, and
STOP push-buttons�
The STOP push-button resets any existing
command and is active both in local and
remote�
If the 3-position selector is in LOCAL, the
OPEN / yES, and CLOSE /NO push-buttons
work as OPEN and CLOSE commands�
If the 3-position selector is in REMOTE or
in Off, the OPEN / yES and CLOSE / NO
push-buttons work as yES and NO to answer
the prompt (next? OK? view?, change? exit?) of
the alphanumeric display�
In Off, the OPEN / yES and CLOSE / NO
push-buttons allow to scroll down the menu,
to view and change the actuator configuration
or to scroll the list of variables, status, and
alarms�
In REMOTE, the above push-buttons allow
scrolling the list of variables, status, alarms
and reports but the actuator configuration
cannot be viewed or changed�
- actuator control
- actuator configuration
- actuator status visualisation
The figures on the following pages describe
the function of each component of the local
operator interface�
three led’s
to indicate the actuator status
according to the following logic:
- green ON/ red Off: the actuator is stopped in
open position
- green Off/ red ON: the actuator is stopped in
closed position
- green Off/ red flashing: the actuator is
running in closing direction
- green flashing/ red Off: the actuator is
running in opening direction
- green ON/ red ON: the actuator is stopped in
intermediate position
- yellow ON: alarm
- yellow flashing: warning
The above color combination is supplied as
standard, but it may be changed (red with
green, green with red, and yellow with red),
during actuator setting operations�
1
3
2
4
5
6
output torque
mot temp
motor speed
term temp
main voltage
log status
current
wireless report
temperature
node report *
time
fDI report *
date
base report
alarm
term report
warning
Ain/Aout report *
Ktemp
The data with * are only present if the relevant