background image

18

To reduce losses during replenishment it is necessary to install the group as close as possible to the pumping point
and to install a suction pipe with a minor number of curvatures that should have a sufficiently wide radius.
Even the diameter of the pipe should be calculated so as to reduce load losses, what requires dimensions greater
than or equal to those of the motor pump aspiration inlet.
In order to avoid the formation of air locks into the suction pipes, these ones must have a positive gradient, from
bottom to top, avoiding countergradients or “goosenecks”, and there must not any infiltration in the connections.
Connect the delivery collector to the distribution collector by interposing vibration-damping joint.
This connection can be done either on the right side or on the left side of the collector by displacing the blind flange
or the threaded cover.

WARNING

It is a good rule to foresee the evacuation of water losses in case of
bad seal of joints, mechanical seal, tanks overflowing.

In the case where there would not be any pumping in close proximity from the group, on the discharge line, the
installation of a test faucet is recommended.
It is necessary to control from time to time the pre - replenishment pressure o

f membrane vessel th

at must be 0.2

bar lower than the minimum closing pressure of the pressure switch calibrated lower.
This control must be done without pressure in the installation or with the tanks disassembled.

Chap.4 – Priming of the group

DANGER

Risk of electrical
discharge

Always shut off the voltage before proceeding to any operation.

WARNING

the group needs to be filled up before putting it in operation. The dry-
operation of the motor pump damages the hydraulic parts.

In case of aspiration with

 positiv suction head, open storage, aqueduct or water pipe under pressure, prime the group

as follows:

- open all valves and remove the priming plugs on the aspiration collector and on the motor pumps
- open the water supply on-off valve until the evacuation of the liquid
- close again the feed faucet and the pumping plugs

In the case where the group supply i

s with lower suction head, u

nderground well or tank, prime the group as follows:

- open all valves and to and remove the priming plugs on the aspiration collector and on the pumps
- fill with water through the suction pipe
- make the necessary topping-up through the priming plugs on the pump casing until complete filling-up
- re assemble the plugs

See fig. 1 - 2

DANGER

Risk of electrical
discharge

WARNING

Check that the power supply is provided with an efficient ground
installation which conforms with the regulations in force.

Check that the voltage and frequency indicated on the data plate
correspond to those of the available power grid.

WARNING

The power supply is equipped with differential circuit breaker with the
sensitivity required by the regulations in force for this type of
equipment.

Chap.5 – Electric connection

See fig.3-4-5 and other schemes reported on the switchboard

GB

Summary of Contents for Nocchi Pressomat

Page 1: ...gs und Wartungsanleitung E Manual de uso y manutenci n NL Handleiding voor gebruik en onderhound PL Recyzny uzywaine i obslugi RUS Bycnherwbb gj ecnfyjdrt b Bycnherwbb gj ecnfyjdrt b Bycnherwbb gj ecn...

Page 2: ...i direktivene gjengitt nedenfor EU VAATIMUSTENMUKAISUUSVAKUUTUS Yhti Pentair International Sarl ilmoittaa omalla vastuullaan ett alla osoitetut tuotteet ovat oleellisten turvallisuus ja terveydensuoj...

Page 3: ...ely the retailer In case of claims contact immediately the retailer within eight days of purchase Chap 2 Limits of use Our pressurization groups are constructed for the raising clean water without sol...

Page 4: ...t pressure in the installation or with the tanks disassembled Chap 4 Priming of the group DANGER Risk of electrical discharge Always shut off the voltage before proceeding to any operation WARNING the...

Page 5: ...Once all the hydraulic and electric connections have been done for the hydraulic priming of the pumps and collectors proceed as follows close all the valves of the distribution system open all the va...

Page 6: ...to 0 OFF From then on the unit will automatically work according to the quantity of water withdrawn by its use Change of the working pressure setup Our units are set and tested during manufacture and...

Page 7: ...small collector by bringing the pressure to the level start pump that we want to assign to pressure switch n 1 tighten screw B of pressure switch n 1 to the point where its electric contact closes ON...

Page 8: ...ped WARNING The calibration values of the pressure switch must be between the minimum and maximum working pressure levels foreseen for the pump used in the unit and reported in the plate applied to th...

Page 9: ...NO Line n 1 COMPRESSOR With keys 16 or 17 it is possible to set the parameter YES or NO YES means that the unit has a pump and an air compressor operated by the same switchboard In this example NO Li...

Page 10: ...essage will appear ENTER TIMING PUMPSN 3s 060 Line n 1 Timing Noparameter Line n 2 PUMPS N 3 s With keys 16 or 17 it is possible to set the parameter to any value between 0 and 255 seconds This indica...

Page 11: ...ollowing message will be displayed In this case both the green led 2 and the red led 5 are lit BEFORETHEBUZZEREMITSTHE8th EIGHTH RING Press key 11 for a few seconds The following message will be displ...

Page 12: ...ted by the same switchboard In the example NO Line n 2 no message After choosing the parameter press key 18 the following message will appear ENTER DELAY FC S 40 ACTIVATION FC s X60 Line n 1 DELAY FC...

Page 13: ...pump will be stopped XXX seconds after having reached the maximum pressure set In the case of this example it is for 40 seconds After choosing the parameter press key 18 the following message will app...

Page 14: ...isplayed M A MANUALE FUNCTION BAR 5 3 The buzzer automatically sounds off and the red led 5 remains turned on Press key 18 for 2 seconds and the following message will be displayed LINEA MAN MAN ENTER...

Page 15: ...r 17 set the number in tens of minimum pressure values for the second pump normally 0 Confirm by pressing key 18 The cursor will change position depending on the number of units involved With keys 16...

Page 16: ...BARs normally 0 3 to 1 0 lower than the value assigned to pump 3 Line n 2 MIN0X XS With keys 16 or 17 set the number in tens of minimum pressure value of the fourth pump normally 0 Confirm by pressin...

Page 17: ...mechanic seal etc it is advisable to provide the machine with devices for the periodic starting of the pump and for the signaling of possible damages These additionally have the followings devices 1 w...

Page 18: ...ch on I ON Replace the disconnected fuses Press the AUT switch Restore the water level GB Theconnectingtubeofthepressure switches are obstructed The pressure switches cable is by passed The push selec...

Page 19: ...129 Fig 2 a...

Page 20: ...130 I Fig 2 b...

Page 21: ...131 Fig 3...

Page 22: ...132 Fig 5...

Page 23: ...133 Fig 4 Fig 6 Fig 7 Fig 8 Fig 9...

Page 24: ...134 Fig 10...

Page 25: ...s t correctement effectu s Si la panne est due des causes de force majeure ou d autres facteurs externes et incontr lables Si le produit est utilis avec des liquides abrasifs ou corrosifs ou diff rent...

Page 26: ...elni a k vetkez iratokat v s rl st igazol sz mla r szletes hibabejelent Niniejsze urz dzenie obj te jest gwarancj prawn zgodnie z przepisami i normami obowi zuj cymi w danym pa stwie w dniu zakupu pok...

Page 27: ...253P8800 PENTAIR INTERNATIONAL S a r l Avenue de Sevelin 18 1004 LAUSANNE Switzerland...

Reviews: