MAINTENANCE INSTRUCTIONS
48
P
ARAMETER
21
–
I
GNITION
S
EQUENCE
S
ETTING
I
GNITION POINT IN
H
Z
6. Use buttons ‘+’ o ‘-’ to modify the value of the parameter
between: min = value of parameter 17; max = value of
parameter 18.
The default value is:
- 110 Hz for Natural Gas;
- 130 Hz for L.P.G.;
7
.
Press and release button ‘S’ to confirm. The parameter
number (21) will appear in the display.
8. Switch off the appliance and switch it back on again to
render the new parameter operative.
P
ARAMETER
22
–
F
AN
F
REQUENCY VALUE DISPLAY
6. Use buttons ‘+’ o ‘-’ to modify the value of the parameter:
- 00 = Off
- 01 = On
If parameter value 01 is selected, during the boiler operation,
the display will show the fan frequency value for 10 min.
7. Press and release button ‘S’ to confirm. The parameter
number (22) will appear in the display.
8. Switch off the appliance and switch it back on again to
render the new parameter operative.
P 21
S
S
S
S
110
00
P 22
110V 60Hz
110V 60Hz
110V 60Hz
110V 60Hz
Summary of Contents for PCC 34-H
Page 8: ...GENERAL INFORMATION 5 ...
Page 9: ...GENERALInformation 6 ING ...
Page 10: ...GENERALInformation 7 ...
Page 11: ...GENERALInformation 8 ...
Page 32: ...INSTALLATION INSTRUCTIONS 29 Venting Pictures Illustrations ...
Page 33: ...INSTALLATION INSTRUCTIONS 30 Included With Each Combination Boiler Is A PAHVK Horizontal Kit ...
Page 37: ...INSTALLATION INSTRUCTIONS 34 ...
Page 38: ...INSTALLATION INSTRUCTIONS 35 ...
Page 67: ...INSTALLATION INSTRUCTIONS 64 INDIRECT FIRED WATER HEATER 6 9 D H W sensor connection ...