MAINTENANCE INSTRUCTIONS
44
P
ARAMETER
4
–
C
ENTRAL HEATING PUMP
6. Use buttons ‘+’ and ‘-‘to modify the value of the parameter:
00 = standard (3 minute default overrun)
01 = permanent (always running)
7. Press and release button ‘S’ to confirm. The parameter
number (4) will appear on the display.
8. Switch off the appliance and switch it back on again to
render the new parameter operative.
P
ARAMETER
5
–
W
ATER HAMMER PREVENTION
6. Use buttons ‘+’ and ‘-‘ to modify the value of the parameter:
00 = off
01 = on (2 second burner delay upon D.H.W. call)
7. Press and release button ‘S’ to confirm. The parameter
number (5) will appear on the display.
8. Switch off the appliance and switch it back on again to
render the new parameter operative.
P
ARAMETER
6
–
C
ENTRAL HEATING TIMER
Electronically timed heating differential
6. Use buttons ‘+’ and ‘-‘to modify the value of the parameter
within the prescribed limits
00 = 0 x 5 sec = 0 sec
90 = 90 x 5 sec = 450 sec (7.5 min)
The default value is 36 = 180 sec = 3 min
7. Press and release button ‘S’ to confirm. The parameter
number (6) will appear on the display.
8. Switch off the appliance and switch it back on again to
render the new parameter operative.
P 04
S
S
S
S
S
S
00
01
P 05
36
P 06
110V 60Hz
110V 60Hz
110V 60Hz
110V 60Hz
110V 60Hz
110V 60Hz
Summary of Contents for PCC 34-H
Page 8: ...GENERAL INFORMATION 5 ...
Page 9: ...GENERALInformation 6 ING ...
Page 10: ...GENERALInformation 7 ...
Page 11: ...GENERALInformation 8 ...
Page 32: ...INSTALLATION INSTRUCTIONS 29 Venting Pictures Illustrations ...
Page 33: ...INSTALLATION INSTRUCTIONS 30 Included With Each Combination Boiler Is A PAHVK Horizontal Kit ...
Page 37: ...INSTALLATION INSTRUCTIONS 34 ...
Page 38: ...INSTALLATION INSTRUCTIONS 35 ...
Page 67: ...INSTALLATION INSTRUCTIONS 64 INDIRECT FIRED WATER HEATER 6 9 D H W sensor connection ...