1020 Mono Filler
15
The parameters are explained in
4
Parameters
These parameters correspond with the parameters in the tree structure of the device
configuration. When using the industrial protocol register functions, each parameter can be
reached using its number.
Some parameters can be reached directly using ASCII, TP protocol, Modbus RTU, Modbus TCP,
Fins, Profibus or EtherNet/IP. The parameters for Profibus or EtherNet/IP are prefixed with
PB
or
EIP
.
Note: when the device is rebooted or the configuration is manually changed, all configuration
parameters are changed back to the value that were last set manually in the configuration.
4.1
Configuration parameters
No. Name
Description
1
Dosing
Select the type of dosing.
•
In => positive dosing (in-dosing)
•
Out => negative dosing (out-dosing)
2
Weighing
Select the type of weighing.
•
Net => the indicator is automatically set to zero before the
dosing starts.
•
Gross => the indicator is not set to zero before the dosing
starts. The product will be added to the scale.
Δ
Not used if out-dosing is selected. In that case weighing is
always Net.
3
Stability
Select the type of stability to determine the end value after
dosing. This parameter works together with the H-Time
parameter.
•
Stable => wait for Stable
•
H-Time => wait for H-Time
•
H-Time + Stable => wait for H-time then Stable
•
H-Time / Stable => wait for H-time or Stable
•
H-Time => wait for Stable then H-time