1020 Mono Filler
16
4
H-time
The time the controller waits before determine the end value.
The H-time works together with the stability parameter.
Δ
Not used if Stability parameter is set to Stable
5
K.E.B. time
Kinetic Energy Blind time is the time in which the kinetic
energy disappears after coarse dosing turns off. The indicator
value will not be read out by the program during this time.
Δ
K.E.B. time must be less than the remaining Fine Time
6
Inflight
correction
The amount of product that falls on/into the weigher after
dosing is stopped. The correction value indicates the strength
of the correction. 0% means fixed inflight.
7
Maximum
inflight
The inflight correction is not able to correct more than the
maximum inflight. If the calculated inflight is 0, the inflight will
not be corrected.
8
Turnover
correction
This correction will automatically correct the turnover value
to reach the needed Fine Time. 0% means fixed turnover.
9
Fine time
This is the ideal fine time to reach a fast dosing cycle.
Δ
The remaining fine time must be more than the K.E.B. time
10 Tolerance
This checks if the dosed weight is within the tolerance. If the
dosed weight is under the setpoint - min. tolerance, the fine
output will turn on until the weight is correct. If the dosed
weight is over the se max. tolerance, an alarm is given
until it‘s accepted by input 2. The minimum and maximum
tolerance can be set in the recipe.
11 Tolerance
interval
The interval time of the fine output (On/Off) in case of a low
tolerance. If the tolerance interval is 0, the fine output is on
until the correct weight is reached.
12 Display hold
After the dosing is finished, the display hold time starts. The
dosed value will be frozen for this time. When a new dosing
starts before the display hold time is elapsed, the hold time
will be cut off.
13 Release valve Select if a release valve is used in the installation.
•
Yes => output 4 is used to activate the release valve
•
No => output 4 is used to activate the indicator alarm
14 Empty level
The value under which the weigher is seen as empty after
release.
Δ
Not used if no release valve is selected