Microdrive Series Instruction Manual
4201-109 Rev I
101
ADJUSTMENTS
Adjustment
10 MTR CUR
(Default)
(= I Inv.)
Setting
245A
Notes
Motor nameplate value.
Adjustment
11 MTR VOLT
(Default)
(=415V)
Setting
380
Notes
Motor nameplate value.
Adjustment
15 ACC1
(Default)
(=10.0Hz/s)
Setting
5.0
Notes
Slower to limit current required to accelerate
pump.
Adjustment
16 DEC1
(Default)
(=10.0Hz/s)
Setting
3.0
Notes
Slower to limit current required to decelerate
pump and to prevent regeneration (VLT).
Adjustment
17 T CONST
(Default)
(= 0.05s)
Setting
0.1
Notes
Value set by experiment - increasing value
improves stability but slows response. Adjust
to achieve good response without instability.
Adjustment
21 MIN FR
(Default)
(= 0.0Hz)
Setting
0.0
Notes
Sets minimum output frequency.
Adjustment
22 MAX FR
(Default)
(= 60Hz)
Setting
50.0
Notes
Reduced to 50Hz to avoid overspeed/overload
of pump/motor.
Adjustment
23 FR F1
(Default)
(= +0.0Hz)
Setting
0.0
Notes
In feedback applications FR F1 should generally
be set equal to the minimum frequency, MIN FR.
Adjustment
24 FR F2
(Default)
(=+60.0Hz)
Setting
50.0
Notes
In feedback applications FR F2 should generally
be set equal to the maximum frequency, MAX
FR.
Adjustment
25 MIN FLUX
(Default)
(=100%)
Setting
100
Notes
If MIN FLUX is set below 100% and the reference
input equals the feedback input, then the motor
voltage will be reduced to improve motor
efficiency. However, this can cause surging
of the motor voltage if the reference or
feedback signals are varying. To avoid surging,
increase MIN FLUX to 100%.
Adjustment
42 DEC3
(Default)
(=10.0Hz/s)
Setting
5.0
Notes
Slower to limit current required to decelerate
pump and to prevent regeneration (VLT).
MODES
Mode
64 REF FR
(Default)
(= 010V)
Setting
010V
Notes
010V is the reference input.
Mode
65 FB SRC
(Default)
(=O/LOOP)
Setting
420mA
Notes
Connects the 420mA input as the feedback
source.
Mode
66 I/P MODE
(Default)
(= 01)
Setting
022 WIRE
Notes
Sets the multi-function inputs up for two wire
control.
Mode
71 REV INHIBIT
(Default)
(=N)
Setting
Y
Notes
Inhibits operation in the reverse direction should
this ever inadvertently be demanded.
1000PPR
14
MOTOR PTC
MOTOR PTC
MODE = 1
4807−076 Rev E
SWITCH INPUT 2
SWITCH INPUT 1
0V
SWITCH INPUT 5
SWITCH INPUT 4
SWITCH INPUT 3
START
STOP
8
9
EMERGENCY STOP
DIRECTION INVERT
STOP/RESET
0V
12
11
10
13
EXAMPLE: TACHO CONTROL
WIRING CONFIGURATION
+10V POTENTIOMETER
0V
TACHO INPUT
TACHO SUPPLY
0V
FREQUENCY OUTPUT
FREQUENCY INPUT
0V
FREQUENCY INPUT
0−10V ANALOGUE O/P
I/O NAME
PDL ENCODER 0300−EN
19
SUPPLY
TACHO INPUT
+12V/50mA MAX
0V
0V
15
16
18
17
0V/−mA
0−10V
+ 4−20mA
F = 26.25 F
21
20
O/P
22
23
+V
0V
A
SOURCE
0−10V=0−100Hz
FUNCTION
24
4−20mA
Summary of Contents for D3-2.5
Page 2: ...Microdrive Series Instruction Manual 4201 109 Rev I 4201 003 Rev A Page 2 of 12...
Page 6: ...Microdrive Series Instruction Manual 4201 109 Rev I 4201 003 Rev A Page 6 of 12...
Page 12: ...Microdrive Series Instruction Manual 4201 109 Rev I 4201 003 Rev A Page 12 of 12...
Page 55: ...Microdrive Series Instruction Manual 4201 109 Rev I 55...
Page 74: ...Microdrive Series Instruction Manual 4201 109 Rev I 74...
Page 75: ...Microdrive Series Instruction Manual 4201 109 Rev I 75...
Page 76: ...Microdrive Series Instruction Manual 4201 109 Rev I 76...
Page 77: ...Microdrive Series Instruction Manual 4201 109 Rev I 77...
Page 78: ...Microdrive Series Instruction Manual 4201 109 Rev I 78...
Page 79: ...Microdrive Series Instruction Manual 4201 109 Rev I 79...
Page 80: ...Microdrive Series Instruction Manual 4201 109 Rev I 80...
Page 81: ...Microdrive Series Instruction Manual 4201 109 Rev I 81...
Page 82: ...Microdrive Series Instruction Manual 4201 109 Rev I 82...
Page 83: ...Microdrive Series Instruction Manual 4201 109 Rev I 83...
Page 112: ...Microdrive Series Instruction Manual 4201 109 Rev I 112...
Page 113: ...Microdrive Series Instruction Manual 4201 109 Rev I 113...