background image

3

4. Pilot. The pilot provides an ignition source for the main burners. Your boiler has either a standing

(continuous) pilot or an intermittent (spark ignited) pilot. The standing pilot should always be lit
while the intermittent pilot ignites only when there is a call for heat and extinguishes when the call
for heat ends. See Figure 8.

5. Gas Valve. The gas valve monitors pilot flame and regulates gas flow to the burners and pilot.

6. Safety Relief Valve. A mechanical device that protects the boiler against excessive pressure. The

safety relief valve can discharge a large amount of steam or hot water – the installer should
provide piping to discharge water near the floor close to a floor drain. If the safety relief valve
discharges water, follow the instructions TO TURN OFF GAS TO APPLIANCE on the Lighting
Instructions affixed to the inside of the removable front jacket panel (see Figures 3 through 5 for
typical lighting instructions), and contact a qualified service agency.

C. Lighting Instructions. Instructions to place the boiler in operation and to turn off the boiler are shown

on the Lighting Instructions Label posted on the inside of the front jacket panel of the boiler. Typical
lighting instructions are shown in Figures 3 through 5.

Figure 1: Control Location

Summary of Contents for SERIES 63

Page 1: ...plier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier Ne pas ranger ou utiliser de la gazoline ou d autres liquides ou g...

Page 2: ...ion resumes automatically when the system pressure falls below the CUT IN pressure 1b Limit Water Boiler An electrical device that automatically interrupts the boiler operation when the water temperat...

Page 3: ...relief valve can discharge a large amount of steam or hot water the installer should provide piping to discharge water near the floor close to a floor drain If the safety relief valve discharges water...

Page 4: ...4 Figure 2 Sequence of Operation Intermittent Pilot...

Page 5: ...5 Figure 3 Operating Instructions Spark Ignition 63 03 thru 64 08 Natural Gas LP Gas 64 09 thru 64 12 LP Gas...

Page 6: ...Figure 4 Operating Instructions Spark Ignition 63 03 thru 64 08 Natural Gas LP Gas 64 09 thru 64 12 LP Gas...

Page 7: ...ace control access panel if applicable 10 Turn on all electrical power to the appliance 11 Set thermostat or operating control to desired setting 12 If the appliance will not operate follow the instru...

Page 8: ...r a NIOSH MSHA approved respirator Wear long sleeved loose fitting clothing and gloves to prevent skin contact Wear eye goggles Minimize airborne dust prior to handling and removal by water misting th...

Page 9: ...ontinuous to chimney with no separations obstructions or sags Vent pipe must be supported at minimum 4 foot intervals and secured with sheet metal screws 2 The vent system must not have signs of conti...

Page 10: ...Inspection and Maintenance Annual For continued safe operation a qualified service agency must provide a more detailed inspection of burners heat exchanger and vent system and provide maintenance as s...

Reviews: