background image

7

       SPRK 7000DERHC 9363R REV.0

FOR YOUR SAFETY READ BEFORE LIGHTING

WARNING:  If you do not follow these instructions exactly, a fire or explosion may 
result causing property damage, personal injury, or loss of life.

OPERATING INSTRUCTIONS

TO TURN OFF GAS TO APPLIANCE

1.  Set the thermostat or operating control to lowest 
     setting.

2.  Turn off all electric power to the appliance if service is 
      to be performed.

3.  If the gas valve is not visible, remove the control  

      access panel.

4.  Turn the gas control knob clockwise            to "OFF".

5.  Replace control access panel, if applicable.

1.  STOP!  Read the safety information above on this 
     label.

2.  Set the thermostat or operating control to lowest 
     setting.

3. Turn off all electric power to the appliance.   

4.  This appliance is equipped with an ignition device 
     which automatically lights the pilot.  Do not try to light 
     the pilot by hand.

  5.  If the gas valve is not visible, remove control access 
      panel.
 
  6.  If the gas control knob is not in the "OFF" postion, 
      turn the knob clockwise          to "OFF".

  7.   Wait five (5) minutes to clear out any gas.  Then smell 
       for gas, including near the floor.  If you smell gas, 
       STOP!  Follow "B" in the safety information above on 
       this label.  If you don't smell gas, go to the next step.

  8.  Turn the gas control knob counterclockwise         to 
      "ON".

  9.  Replace control access panel, if applicable.

10.  Turn on all electrical power to the appliance.

11.  Set thermostat or operating control to desired setting.
 
12.  If the appliance will not operate, follow the 
       instructions "To Turn Off Gas To Appliance"
       and call your service technician or gas supplier.

A.  This appliance is equipped with an ignition device 
      which automatically lights the pilot.  Do not try to
      light the pilot by hand.

B.  BEFORE OPERATING smell all around the appliance   
      area for gas.  Be sure to smell next to the floor 
      because some gas is heavier than air and will settle
      on the floor.

      WHAT TO DO IF YOU SMELL GAS

             Do not try to light any appliance
         
             Do not touch any electric switch;
             do not use any phone in your building.

           Immediately call your gas supplier from a    
           neighbor's phone.  Follow the gas supplier's 
           instructions.

           If you cannot reach your gas supplier, 
           call the fire department.

C.  Use only your hand to push in or turn the gas control 
      knob.  Never use tools.  If the knob will not push in or 
      turn by hand, don't try to repair it, call a qualified 
      service technician.  Force or attempted repair may 
      result in a fire or explosion.

D.  Do not use this appliance if any part has been under 
      water.  Immediately call a qualified service technician 
      to inspect the appliance and to replace any part of the 
      control system and any gas control which has been   
      under water.

Gas Control Knob 
(shown in "OFF" 
position)

Figure 5: Operating Instructions, Spark Ignition

64-09 thru 64-12 Natural Gas

Summary of Contents for SERIES 63

Page 1: ...plier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier Ne pas ranger ou utiliser de la gazoline ou d autres liquides ou g...

Page 2: ...ion resumes automatically when the system pressure falls below the CUT IN pressure 1b Limit Water Boiler An electrical device that automatically interrupts the boiler operation when the water temperat...

Page 3: ...relief valve can discharge a large amount of steam or hot water the installer should provide piping to discharge water near the floor close to a floor drain If the safety relief valve discharges water...

Page 4: ...4 Figure 2 Sequence of Operation Intermittent Pilot...

Page 5: ...5 Figure 3 Operating Instructions Spark Ignition 63 03 thru 64 08 Natural Gas LP Gas 64 09 thru 64 12 LP Gas...

Page 6: ...Figure 4 Operating Instructions Spark Ignition 63 03 thru 64 08 Natural Gas LP Gas 64 09 thru 64 12 LP Gas...

Page 7: ...ace control access panel if applicable 10 Turn on all electrical power to the appliance 11 Set thermostat or operating control to desired setting 12 If the appliance will not operate follow the instru...

Page 8: ...r a NIOSH MSHA approved respirator Wear long sleeved loose fitting clothing and gloves to prevent skin contact Wear eye goggles Minimize airborne dust prior to handling and removal by water misting th...

Page 9: ...ontinuous to chimney with no separations obstructions or sags Vent pipe must be supported at minimum 4 foot intervals and secured with sheet metal screws 2 The vent system must not have signs of conti...

Page 10: ...Inspection and Maintenance Annual For continued safe operation a qualified service agency must provide a more detailed inspection of burners heat exchanger and vent system and provide maintenance as s...

Reviews: