  Thermific

®

 Gas-Fired Boiler

Installation

Page  5

with the application of heat.  Refer to the
manufacturer's instructions.  Wrap the joint with
aluminum tape which is backed with an adhesive on
the contact side.

3.2.5  Inlet Damper and Auxiliary Control
Panel (optional)

Note:

The inlet damper assembly and control panel will
prevent the flow of cold air through the boiler during
the off cycle and prevent freeze up.  These two items
are

optional

 in all installations.

Refer to Section 4.1 for a description of the control
sequence applicable to the inlet damper.

The damper must be field installed into a section of
horizontal or vertical inlet ductwork.  Orient the
damper such that the arrow points towards the boiler.

3.2.5.1  Field Wiring to Auxiliary Control Panel

The auxiliary control panel controls the inlet damper
(if used).  The auxiliary control panel does not have to
be mounted on or near the boiler; it can be remotely
mounted.

Use 16GA MTW Wire for all field wiring.  See
Section 6 for the logic and wiring diagrams of this
auxiliary control panel and the sealed combustion
boilers.

There are five (5) field run wires between the boiler
and its auxiliary control panel; three (3) for main
power supply and two (2) wires for boiler
interconnect.

1. The main power supply (G/H/N) must come from

the same boiler that the damper is connected to.

2. Remove the blue jumper wire in the terminal block

on the boiler when wiring.

There are also five (5) field run wires between the
auxiliary control panel and the inlet damper assembly;
three (3) to the damper actuator and two (2) to the
limit switch.

1. Terminals for the damper actuator:

DO = Damper Open (CW)
DC = Damper Closed (CCW)
DN = Neutral/Common

2. Terminals for the limit (end) switch

SI = N.O. (Normally Open)
S2 = Common

3.3  E

XHAUST 

V

ENTING

S

YSTEM

3.3.1  System Design - Materials, Length, Size,
and Construction

The flue gas outlet (exhaust vent) must be designed to
comply with UL 1738 and ULC-636.  (Refer to
Section 1.1.2 for situations where alternate compliance
may be permitted.)  The exhaust vent can be run
horizontally or vertically.

The vent must be sized according to the vent
manufacture's recommendations.  Consult the vent
supplier for correct sizing and structural support
requirements.  Vent diameter is dictated by the length
and height of horizontal and vertical portions of the
vent installation and materials of construction.  Design
calculations should be based on a negative 0.03 W.C.
with a stack temperature of 325º F (gross) and a CO

2

level of 7.6%; (these values are to be used for vent
sizing calculations.)  The 

maximum

 allowable length

of the vent duct, including the boot tee/135º tee (not a
standard tee) and the termination is 100 equivalent
feet.  See Section 3.4.5 for the equivalent length of the
fittings.

3.3.2  Flue Gas Outlet Duct

The installation must follow the vent manufacturer's
instructions in all respects including proper joining and
sealing of the tubing and fittings, clearances to
combustible materials and installation of firestops.

Summary of Contents for DVSCM-02

Page 1: ...KELLEY THERMIFIC DIRECT VENT SEALED COMBUSTION GAS FIRED BOILER Supplement to the standard Installation and Owner s Manual TBIG Latest Edition Installation Date _______________________ 100 Burson Stre...

Page 2: ...Hi Lo 15 6 1c Lo Hi Lo IRI 17 6 1d On Off Series 1500 1700 2000 19 6 1e On Off IRI Series 1500 1700 2000 21 6 2 Auxiliary Control Panel 23 6 2 1 On Off Auxiliary Control Panel 23 Reorder No 6020 V2WH...

Page 3: ...dard B vent is not approved Proper vent sizing by the vent manufacturer s recommendation must be followed The exhaust vent may be run horizontally or vertically The maximum allowable length of the exh...

Page 4: ...stallation and Owner s Manual TBIG Both documents must be used together This companion document describes those safety installation adjustment and maintenance procedures which differ from the standard...

Page 5: ...all Galvanized Duct Proper sealing of the tubing is necessary to prevent flow of combustion air from conditioned space If single wall galvanized tubing is used GE RTV 102 silicone sealant or equivalen...

Page 6: ...et on Series 1500 1700 and 2000 A separate box of accessories is sent with the boiler 1 Attach the 6 inch diameter end of the custom transition duct and the extension to the collar using a minimum of...

Page 7: ...the boiler when wiring There are also five 5 field run wires between the auxiliary control panel and the inlet damper assembly three 3 to the damper actuator and two 2 to the limit switch 1 Terminals...

Page 8: ...135 tee must be installed not a standard tee If the flue gas exhaust is to be routed through the sidewall a minimum vertical rise of 6 feet is required from the outlet of the boot tee 135 tee to the i...

Page 9: ...referred method to terminate the exhaust vent is with a rain cap to minimize the drippage of condensate onto the roof and ice build up The rain cap should be an unrestrictive type similar to the figur...

Page 10: ...a 4 foot horizontal distance is maintained electric meters gas meters regulators and relief equipment 3 4 2 Rooftop Installations 4 min above snow line 10 min 4 min Flue Gas Outlet Combustion Air Inle...

Page 11: ...indicator will remain on until sufficient air flow is sensed If the air flow switch is not closed in 120 seconds the time delay relay will open its normally closed contacts This will turn off the blo...

Page 12: ...0 7 8 6 9 7 8 6 8 7 9 6 7 8 6 6 8 6 5 8 1 6 4 8 1 6 3 8 2 6 2 8 2 6 1 8 3 6 8 3 Important measure combustion air temperature at the unit do not assume the combustion air temperature is the same as the...

Page 13: ...Thermific Gas Fired Boiler Wiring Diagrams Page 11 6 0 WIRING DIAGRAMS 6 1 ON OFF SERIES 700 1000 1200 Wiring Diagram...

Page 14: ...Thermific Gas Fired Boiler Wiring Diagrams Page 12 6 1 ON OFF SERIES 700 1000 1200 Logic Diagram...

Page 15: ...Thermific Gas Fired Boiler Wiring Diagrams Page 13 6 1A ON OFF IRI SERIES 700 1000 1200 Wiring Diagram...

Page 16: ...Thermific Gas Fired Boiler Wiring Diagrams Page 14 6 1A ON OFF IRI SERIES 700 1000 1200 Logic Diagram...

Page 17: ...Thermific Gas Fired Boiler Wiring Diagrams Page 15 6 1B LO HI LO Wiring Diagram...

Page 18: ...Thermific Gas Fired Boiler Wiring Diagrams Page 16 6 1B LO HI LO Logic Diagram...

Page 19: ...Thermific Gas Fired Boiler Wiring Diagrams Page 17 6 1C LO HI LO IRI Wiring Diagram...

Page 20: ...Thermific Gas Fired Boiler Wiring Diagrams Page 18 6 1C LO HI LO IRI Logic Diagram...

Page 21: ...Thermific Gas Fired Boiler Wiring Diagrams Page 19 6 1D ON OFF SERIES 1500 1700 2000 Wiring Diagram...

Page 22: ...Thermific Gas Fired Boiler Wiring Diagrams Page 20 6 1D ON OFF SERIES 1500 1700 2000 Logic Diagram...

Page 23: ...Thermific Gas Fired Boiler Wiring Diagrams Page 21 6 1E ON OFF IRI SERIES 1500 1700 2000 Wiring Diagram...

Page 24: ...Thermific Gas Fired Boiler Wiring Diagrams Page 22 6 1E ON OFF IRI SERIES 1500 1700 2000 Logic Diagram...

Page 25: ...Thermific Gas Fired Boiler Wiring Diagrams Page 23 6 2 AUXILIARY CONTROL PANEL 6 2 1 On Off Auxiliary Control Panel...

Page 26: ...Page 24...

Reviews: