P
AGE
13
1
2
3
4
D
C
B
A
RELAY A
115
230
VAC
CJC
SIGNAL -
MADE IN U.S.A.
GROUND
INPUT RATINGS:
115/230 VAC 50/60 HZ 15VA MAX
RELAY OUTPUT RATINGS:
115VAC 5.0A RESISTIVE
230VAC 2.5A RESISTIVE
230VAC 1/8 HP
115/230VAC 250VA
MAXIMUM AMBIENT : 55
°
C
5
6
8
7
E
F
G
H
RETURN
OUT1
4-20mA
+
OUT2
4-20mA
+
REMOTE
SETPT +
SERIAL A
SERIAL B
POS.PROP.
WIPER
POS.PROP.
HIGH
RELAY C
RELAY B
FIGURE 2-4 WIRING LABEL
Input Connections 2.3
In general, all wiring connections are made to the instrument after it is installed.
Avoid
electrical shock. AC power wiring must not be connected to the source distribution
panel until all wiring connection procedures are completed.
2.3.1 INPUT CONNECTIONS
FIGURE 2-5
AC Power
Connect 115 VAC hot and neutral to terminals B and A respectively as illustrated below.
Connect 230 VAC as described below. Connect Earth ground to the ground screw as shown.
115 VAC INSTRUMENT VOLTAGE
L1
L2
B
A
GROUND
.5 AMP*
FUSE
Rear View
*Supplied by customer
230 VAC INSTRUMENT VOLTAGE
B
A
GROUND
L1
L2
.25 AMP*
FUSE
Rear View
*Supplied by the customer