Appendix D - Specifications
Input Specifications
THERMOCOUPLE
TYPE
RANGE
TYPE
RANGE
J
-130 TO 760C
E
0 TO 750C
-200 TO 1400F
0 TO 1400F
K
-130 TO 1370C
B
200 TO 1800C
-200 TO 2500F
400 TO 3300F
T
-200 TO 400C
N
0 TO 1300C
-330 TO 750F
0 TO 2370F
R
200 TO 1650C
C
200 TO 2300C
400 TO 3000F
390 TO 4170F
S
200 TO 1650C
400 TO 3000F
RTD
VOLTS
MILLIVOLTS
100 ohm
0 to 5 VDC
0 to 25 mVDC
(.00385 OHM/OHM/C)
1 to 5 VDC
0 to 50 mVDC
-140 to 400C
10 to 50 mVDC
-220 to 750F
MILLIAMPS
REMOTE SETPOINT
* 0 to 20 mADC
0 to 5 VDC
1 to 5 VDC
* 4 to 20 mADC is accommodated via the 1-5 VDC with the
addition of a shunt resistor.
SENSOR FAULT DETECTION
Displays Hi or Lo process input for thermocouple or RTD inputs (10% above or below range)
and sensor break, SnSr. On/Off outputs and proportional outputs go off. Sensor fault
detection is not functional for 0 to 5 VDC.