Output Specifications
CONTROL OUTPUT 1 AND 2
Relay Output
SPST
115 VAC: 5.0 A Resistive; 1/8HP or 250 VA
230 VAC: 2.5 A Resistive; 1/8HP or 250 VA
SSR Driver
Open collector output
Short circuit protected at 100 mA maximum
Provides 4 VDC at 20 mA or 3 VDC at 40 mA
Current Output
0-20mADC or 4-20 mADC into 650 ohms maximum.
ALARM OUTPUT
Relay Output
SPST
115 VAC: 5.0 A Resistive; 1/8HP or 250 VA
230 VAC: 2.5 A Resistive; 1/8HP or 250 VA
SSR Driver
Open collector output
Short circuit protected at 100 mA maximum
Provides 4 VDC at 20 mA or 3 VDC at 40 mA
Display Specifications
Digital Display
Four (4) 7 segment LED’s each; .56 inches high
Status Indicators Individual LED indicators for Setpoint, Out 1, Out 2, Manual,
Alarm, Degrees F, Degrees C, or Engineering Units, minus sign for negative values
Alarm Adjustment Specifications
Process Alarm
-9999 to 9999 units
Deviation Alarm
-3000 to 3000 units
Deviation Band Alarm
1 to 3000 units
Control Adjustments Specifications
On/Off Hysteresis
0 to 300 units
Proportional Band
1 to 3000 units
Manual Reset
-1500 to 1500 units
Auto Reset
0.0 to 100.0 repeats/minute
Rate
0.0 to 10.0 minutes
Cycle Time
1 to 240 seconds
Position Proportioning Sensitivity
0.0 to 50.0 %
First Output Position
-1000 to 1000 units
Spread
-1000 to 1000 units