PF6000X
Barrier Sequences Explained
Standard Barrier Entry “One Way“ Operation
1.
Barrier raise requested (keypad/swipe card etc).
2.
Barrier Raised.
3.
Barrier “No Passage” timer started.
4.
Car moves onto safety loop (free exit loop inhibited, no passage timer cancelled).
5.
Car moves o ffof safety loop.
6.
Barrier lowered.
Safety Loop
Free Exit Loop
ENTR
Y
EXIT
B2A Sequence
Where B is the safety loop, under the
barrier, and A is the free exit loop, the other
side of the barrier.
B2A (Enter Site)
1. Barrier Raise Request (Keypad/Swipe
Card etc)
2. Barrier Raised
3. Barrier “No Passage” timer started
4. Should “No Passage Timer” elapse
before safety loop seen, go to 9
5. Car move onto safety loop (free exit loop
inhibited, no passage timer cancelled)
6. Car moves o ffsafety loop
7. Car move onto free exit loop
8. Car moves o ffof free exit loop
9. Free exit loop active again
10. Barrier Lowered
A2B Sequence(Leave Site)
1. Car moves onto free exit loop
2. Barrier Raised
3. Barrier “No Passage” timer started
4. Should “No Passage Timer” elapse
before safety loop seen, go to 9
5. Car move onto safety loop (no passage
timer cancelled)
6. Car moves o ffof safety loop
7. Safety Close timer started
8. Safety Close timer elapses
9. Barrier Lowered
Summary of Contents for PF6000X
Page 1: ...PF6000X Automatic Barrier Rev 1 0 Installation Operation Maintenance Manual ...
Page 11: ...PF6000X Handing Change Procedure ...
Page 12: ...PF6000X Handing Change Procedure ...
Page 13: ...PF6000X Handing Change Procedure ...
Page 14: ...PF6000X Barrier Manual Release Procedure ...
Page 15: ...PF6000X Straining Wire Assembly ...
Page 23: ...PF6000X Loop Detector Guide Relay Functionality Diagnostics ...
Page 28: ...PF6000X Safety Edge Setup ...
Page 29: ...PF6000X Safety Edge Setup ...