19
SPL040---060
English
6
Maintenance
a) The machine is designed and built to guarantee continuous
operation; however, the life of its components depends on the
maintenance performed;
b) when requesting assistance or spare parts, identify the ma-
chine (model and serial number) by reading the dataplate lo-
cated on the unit.
c) Circuits containing 6 kg or more of refrigerant fluid are
checked to identify leaks at least once a year.
Circuits containing 30 kg or more of refrigerant fluid are
checked to identify leaks at least once every six months.
(CE842/2006 art. 3.2.a, 3.2.b).
d) For machines containing 3 kg or more of refrigerant fluid, the
operator must keep a record stating the quantity and type of
refrigerant used, an quantities added and that recovered dur-
ing maintenance operations, repairs and final disposal
(CE842/2006 art. 3.6). An example of this record sheet can be
downloaded from the site: www.dh---hiross.com.
6.1
General instructions
!
Before any maintenance, make sure:
S
the pneumatic circuit is no longer pressurized;
S
the dryer is disconnected from the main power supply.
Y
Always use the Manufacturer’s original spare parts: other-
wise the Manufacturer is relieved of all liability regarding ma-
chine malfunctioning.
Y
In case of refrigerant leakage, contact qualified and author-
ized personnel.
Y
The Schrader valve must only be used in case of machine
malfunction: otherwise any damage caused by incorrect refriger-
ant charging will not be covered by the warranty.
6.2
Refrigerant
Z
Charging: any damage caused by incorrect refrigerant replace-
ment carried out by unauthorized personnel will not be covered
by the warranty.
Y
At normal temperature and pressure, the R134a refrigerant
is a colourless gas classified in SAFETY GROUP A1 --- EN378
(group 2 fluid according to Directive PED 97/23/EC);
GWP (Global Warming Potential) = 1300.
!
In case of refrigerant leakage, ventilate the room.
6.3
Preventive Maintenance Programme
To guarantee lasting maximum dryer efficiency and reliability:
Maintenance
Activity Description
Maintenance Interval
(standard opration conditions)
Activity
Da
ily
W
eekly
4M
on
th
s
12
M
ont
hs
Check POWER ON indicator is lit.
Check control panel indicators.
Check condensate drain.
Clean condenser fins.
Check electrical absorption.
Depressurize the dryer.
Complete drain maintenance.
Depressurize the dryer.
Replace pre--- and post---filter ele-
ments.
check
service
The following are available (see par. 8.4):
a)
service kits
1. compressor kits;
2. fan kits;
3. automatic expansion valve kit
s;
4. hot gas valve kits;
b)
individual spare parts.
6.4
Dismantling
Z
The refrigerant and the lubricating oil contained in the circuit
must be recovered in conformity with current local environmen-
tal regulations.
The refrigerant fluid is recovered before final scrapping of the
equipment (CE 842/2006 art.4.4).
%
Recycling
Disposal
structural work
steel/epoxy---polyester resins
exchanger
aluminium
pipes
aluminium/copper
drain
polyamide
exchanger insulation
EPS (sintered polystyrene)
pipe insulation
synthetic rubber
compressor
steel/copper/aluminium/oil
condenser
steel/copper/aluminium
refrigerant
R134a
valves
brass
electrical cables
copper/PVC
Summary of Contents for STARLETTE PLUS SPL040
Page 2: ......
Page 66: ...SPL040 060 64 7 Z 50 C Z HT PV TV Z HT Z Z Z Z Z...
Page 76: ...SPL040 060 74 8 6 Dimensional drawing inches mm...
Page 77: ...75 SPL040 060 8 7 Refrigerant circuit SPL040 SPL050 060...
Page 78: ...SPL040 060 76 8 8 Wiring diagram SPL040...
Page 79: ...77 SPL040 060 Wiring diagram SPL050...
Page 80: ...SPL040 060 78 Wiring diagram SPL060...
Page 84: ...EL 8 8 C M R 12 18 a Parker 4 b Quasar LCD c d e f g 8 8 Passport 1 2 3 4 5 a b 196 2003 4...
Page 96: ...RU 8 8 C M R 12 18 a Parker b Quasar LCD c d e f g 8 8 1 2 3 4 5 a b 196 2003...