2 4

OEM-AT6400 Installation Guide

signal wiring, especially when they are tied in the same
wiring bundle or conduit.

When this kind of problem occurs, you should consider
shielding signal cables or isolating the signals.  A proper
shield surrounds the signal wires to intercept electrical
fields, but this shield must be tied to Earth to drain the
induced voltages.  At the very least, wires should be run
in twisted pairs to limit straight line antenna effects.

Even the worst noise problems in environments near 600
amp welders and 25kW transmitters have been solved
using enclosures, conduit, optical isolation, and single-
point ground techniques.

Ground Loops
Ground Loops are the most mysterious noise problems.
Symptoms like garbled transmissions and intermittent
operation are typical.

The problem occurs in systems where multiple Earth
ground connections exist, particularly when these
connections are far apart.

The way to test for and ultimately eliminate a ground loop
is to lift or 

cheat Earth ground connections in the system

until the symptoms disappear.

Defeating Noise

The best time to handle electrical noise problems is before
they occur.  When a motion system is in the design
process, the designer should consider the following set of
guidelines for system wiring (in order of importance):

Put surge suppression components on all electrical
coils:  Resistor/capacitor filters, MOVs, Zener and
clamping diodes.

Shield all remote connections, use twisted pairs.
Shields should be tied to Earth at one end.

Put all microelectronic components in an enclosure.
Keep noisy devices outside. Watch internal
temperature.

Ground signal common wiring at one point.  Float this
ground from Earth if possible.

Tie all mechanical grounds to Earth at one point.  Run
chassis and motor grounds to the frame, and the
frame to Earth.

Isolate remote signals.  Solid state relays or opto
isolators are recommended.

Filter the power line.  Use common RF filters, and use
an isolation transformer for worst case.

A noise problem must be identified before it can be
solved.  The obvious way to approach a problem situation
is to eliminate potential noise sources until the symptoms
disappear, as in the case of ground loops.  When this is
not practical, use the above guidelines to make the
installation as robust as possible.

R e f e r e n c e s

Information about the equipment referred to may be
obtained by calling the numbers listed below.

Corcom line filters, (214) 386-5515

Opto-22 optically isolated relays, (408) 496-6611

Crydom optically isolated relays, (415) 463-2250

Potter Brumfield optically isolated relays, (812) 386-
1000

Teal power line isolation filters, (800) 888-8325

Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Summary of Contents for Compumotor OEM-AT6400

Page 1: ... underutilized and idle equipment along with credit for buybacks and trade ins Custom engineering so your equipment works exactly as you specify Critical and expedited services Leasing Rentals Demos In stock Ready to ship TAR certified secure asset solutions Expert team I Trust guarantee I 100 satisfaction All trademarks brand names and brands appearing herein are the property of their respective ...

Page 2: ...pumo tor Compumotor Division Parker Hannifin Corporation p n 88 014587 01A May 1995 OEM AT6400 Installation Guide Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...

Page 3: ...nel North America and Asia Compumotor Division of Parker Hannifin 5500 Business Park Drive Rohnert Park CA 94928 Telephone 800 358 9070 or 707 584 7558 Fax 707 584 3793 FaxBack 800 936 6939 or 707 586 8586 BBS 707 584 4059 e mail tech_help cmotor com Internet http www compumotor com Europe non German speaking Parker Digiplan 21 Balena Close Poole Dorset England BH17 7DX Telephone 44 0 1202 69 9000...

Page 4: ...s how to install and troubleshoot the OEM AT6400 hardware Programming related issues are covered in the 6000 Series Programmer s Guide and the 6000 Series Software Reference Guide What You Should Know To install and troubleshoot the OEM AT6400 you should have a fundamental understanding of IBM PC compatible computer hardware and software operations Basic electronics concepts such as voltage switch...

Page 5: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...

Page 6: ...specifications table PC card installation procedures Mounting procedures Electrical connection procedures including specifications Installation test procedures Preparation for what to do next Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...

Page 7: ... remove power to the computer before Installing or removing the OEM AT6400 PC card Adjusting the DIP switches on the OEM AT6400 PC card after it is installed in the computer Connecting electrical devices to the OEM AT6400 PC card after it is installed in the computer Electrical Noise The OEM AT6400 does not have the I O optical isolation circuitry that is standard for most of the 6000 Series index...

Page 8: ...tible with internal 6 8 KΩ pull ups to IN P terminal connect to internal 5V or external power supply Voltage range 0 24V Outputs 4 General Purpose Programmable Open collector output with 4 7 KΩ pull ups Can be pulled up by connecting OUT P to 5V or to user supplied voltage of up to 24V Max voltage in the OFF state not sinking current 24V max current in the ON state sinking 30mA Step Direction Diff...

Page 9: ... Prototype Card 800 815 320 32F Hard Disk XT 888 895 378 37F Parallel Printer 896 911 380 38F SDLC 928 943 3A0 3AF SDLC 944 955 3B0 3BB Monochrome Card 956 959 3BC 3BF Parallel Printer 960 975 3C0 3CF EGA Card 976 991 3D0 3DF CGA Card 1000 1007 3E8 3EF Serial Port 3 1008 1015 3F0 3F7 Floppy Disk 1016 1023 3F8 3FF Serial Port 1 Computer I O Address Space Map Address Range Description Decimal Hex IN...

Page 10: ...he connector can be temporarily pushed back through one of the empty adjacent access slots to secure it See the drawing on the next page St ep 7 Insert the bottom corner of the OEM AT6400 PC card into the card guide slot near the front of the computer Ease both ends of the card simultaneously down into the computer until the card s edge connector reaches the computer s mating connector see drawing...

Page 11: ...VM60 ADAPTOR for screw terminal connections 60 pin mating connector P IN OU TS Pin In Out Description Pin In Out Description 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 Output Output Output Output Output Output Output Output Input Input Input Input Input Input Input Input Input Input Input Input Input Input Input Input Input Input Input Input Input Input St...

Page 12: ...igh signal on Direction 1 specifies motion in the positive direction for Axis 1 Low signal on Direction 1 specifies motion in the negative direction for Axis 1 Signal levels Low 1 0VDC 30mA High 3 5VDC 30mA 4 OUT Direction 1Return Differential output Low signal on Direction 1 specifies motion in the positive direction for Axis 1 High signal on Direction 1 specifies motion in the negative direction...

Page 13: ...eference position The active level default is active low can be changed with the HOMLVL command Internal Schematic 74HCxx 5V connected to AUX P sourcing current Provides 5V power to the POS NEG and HOM input pull up resistors As an alternative you can connect AUX P to an external power supply of up to 24VDC NOTE AUX P is also the pull up for the TRG inputs SINKING CURRENT To make these inputs sink...

Page 14: ...s GND 74HCxx 6 8 KΩ 47 KΩ Trigger Input Connection Ground Connection Output Ground 5VDC AUX P 5V GND Pulled down to ground sinking OEM AT6400 GND V1 R1 Connection to a Combination of Sinking Sourcing Outputs Typical value for R 450Ω assuming R1 0 Note The value of R may vary depending on the value of R1 and V1 Electronic Device Out 5 24 Volts GND 74HCxx 6 8 KΩ 47 KΩ Trigger Input Connection Ground...

Page 15: ... but can be changed to active high with the INLVL command OUTPUT PIN OUTS SPECIFICATIONS Pin Function Internal Schematic Specifications 40 5 VDC 42 OUT P Output Pullup 44 Output 1 LSB 46 Output 2 48 Output 3 50 Output 4 MSB 7406 4 7 KΩ Output Connection Ground Connection 5VDC OUT P 5V GND Pulled up to 5V OEM AT6400 GND GND Open Collector GND External Supply up to 24VDC Open collector output Pull u...

Page 16: ... V1 R1 R PROGRAMMING TIP Connecting to a sinking output Set the input s active level to low with the INLVL command Ø active low Connecting to a sourcing output Set the input s active level to high with the INLVL command 1 active high Thus when the output is active the TIN status command will report a 1 indicates that the input is active regardless of the type of output that is connected Details on...

Page 17: ...2 Ground Connection Input Ground 7406 4 7 KΩ GND open collector Sourcing Input Sinking Input Connection to an Inductive Load active low Output Connection OUT P 5V GND OEM AT6400 7406 4 7 KΩ 5VDC GND External Supply up to 24VDC open collector Use an external diode when driving inductive loads Connect the diode in parallel to the inductive load attaching the anode to the OEM AT6400 output and the ca...

Page 18: ...g the operating system the status LED will turn green indicating the system is ready for operation If the LED does not turn green after downloading the operating system an error has occurred The download program AT6400 issues an error message if it cannot find the card or if the download operation is not successful refer also to the Downloading Error Table provided in Chapter 2 Board Monitor Alarm...

Page 19: ...ve the other end of the shield disconnected Do not route I O signals in the same conduit or wiring trays as high voltage AC wiring or motor wiring Provide some form of isolation for the I O preferably optical isolation to reduce the effects of noise in your system Reducing noise on limit and trigger inputs If you are experiencing noise problems try adding resistors to reduce noise sensitivity see ...

Page 20: ...P switch setting default is 768 decimal just press ENTER If you changed the DIP switch see page 4 type in the new address and press ENTER The program displays this menu Parker Compumotor s Motion and I O Test Program 1 Limits 2 Pulse Cutoff P CUT Not applicable for OEM AT6400 3 Programmable Inputs 4 Joystick Inputs Not applicable for OEM AT6400 5 Programmable Outputs 6 Encoders Not applicable for ...

Page 21: ...ram tester You can create your own test panel to run your programs and check the activity of I O motion system status etc This can be invaluable during start ups and when fine tuning machine performance On line context sensitive help and technical references These on line resources provide help information about Motion Architect as well as interactive access to the contents of the 6000 Series Soft...

Page 22: ...al noise Diagnostic LED Test program Motion Architect Test Panel Technical support Solutions to common problems Corrective actions in response to operating system download errors Product repair procedure Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...

Page 23: ...em solutions contained in this chapter If the problem persists contact your local technical support resource see Technical Support below Reducing Electrical Noise Refer to the guidelines on page 14 and in Appendix A General information on reducing electrical noise can be found in the Engineering Reference section of the Parker Compumotor Digiplan Positioning Control Systems and Drives Catalog Diag...

Page 24: ...ress conflict 3 OEM AT6400 card not properly seated 1 Select correct address for communication program 2 See Address Selection section below 3 Seat board properly in slot Apply pressure directly over area with gold card edge fingers Computer will not boot with OEM AT6400 installed 1 Interrupt conflict 2 See problem Communication Errors 1 a Turn interrupt DIP switches OFF 1 b See Interrupt Selectio...

Page 25: ...ice connect IN P to 5V supply on the OEM AT6400 card or other positive supply 1b When inputs will be pulled to 5V or higher by an external device connect IN P to 0V 2 Connect external power supply s ground to OEM AT6400 s ground GND 3 Check wiring for opens shorts and mis wired connections Programmable outputs not working 1 Output connected such that it must source current pull to positive voltage...

Page 26: ...in increments of 8 5 Unknown Option An unknown option was specified on the AT6400 EXE command line 6 Base Port Address Greater than 1024 The base port address is too high Specify an address between 768 and 1024 decimal with the PORT parameter 7 Base Port Address Less than 255 The base port address is too low Specify an address between 768 and 1024 decimal with the PORT parameter 8 Base Port Addres...

Page 27: ...d line arguments Obtain a ROM update from the factory 23 Card ROMS Unsupported Option Requested The card ROMS do not support the option specified on the command line Obtain a ROM update from the factory 24 NULL Error Product Repair Procedure Step 1 Obtain the serial number and the model number OEM AT6400 of the defective unit and secure a purchase order number to cover repair costs in the event th...

Page 28: ...e disturbances are created on signal and ground wires that are connected to the OEM AT6400 This kind of noise can get into logic circuit ground or into the processor power supply and scramble the program The problem here is that control equipment often shares a common DC ground wire that may be connected to several devices such as a DC power supply programmable controller remote switches etc When ...

Page 29: ...r system wiring in order of importance Put surge suppression components on all electrical coils Resistor capacitor filters MOVs Zener and clamping diodes Shield all remote connections use twisted pairs Shields should be tied to Earth at one end Put all microelectronic components in an enclosure Keep noisy devices outside Watch internal temperature Ground signal common wiring at one point Float thi...

Page 30: ...ing operating system errors 21 from Motion Architect 16 LED status 20 problems 20 drive connections 7 E Earth AC power ground 23 Earth ground 24 edge connector PC card 5 electric codes i electrical noise 2 18 suppressing 14 electro static discharge ESD 5 environmental specifications 3 extending I O cables 14 externally conducted noise 23 F factory set DIP switches 4 FAX number for technical suppor...

Page 31: ...ice connecting to 12 sinking output device connecting to 9 11 software update from BBS 16 19 sourcing input device connecting to 12 sourcing output device connecting to 9 11 specifications overall list of 3 status commands see also test on page 15 and Software Reference Guide axis see TAS command limit switches see TLIM command programmable inputs see TIN command programmable outputs see TOUT comm...

Page 32: ...ve low Step pulse width is 0 3 µs to 20 µs depends on the value of the PULSE command default is 0 3 µs Step or Direction pins 1 3 5 7 9 11 13 or 15 Drive Outputs 5VDC GND GND 5VDC Step or Direction pins 2 4 6 8 10 12 14 or 16 HCMOS compatible levels Low 1 00V High 3 25V 1 2 59 60 Pin Function Pin Function 1 Step 1 2 Step 1 3 Direction 1 4 Direction 1 5 Step 2 6 Step 2 7 Direction 2 8 Direction 2 9...

Page 33: ...quipment Have surplus equipment taking up shelf space We ll give it a new home Learn more Visit us at artisantg com for more info on price quotes drivers technical specifications manuals and documentation Artisan Scientific Corporation dba Artisan Technology Group is not an affiliate representative or authorized distributor for any manufacturer listed herein We re here to make your life easier How...

Reviews: