11. How to connect and configure a Run/Stop switch
with Forward/Reverse selection

If this is unsuitable for the application, remote
switches can be used instead.

The procedure described in section 7 enables
Run/Stop operation via the red and green
buttons on the Inverter keypad.

When set to operate in this way, the Inverter
can no longer be operated via the integrated
keypad.

This section explains how to enable 2-wire
control with Run/Stop and Forward/Reverse
commands via separate selector switches.

Parameter

Description

How to set

F208

Two-line/three-line control

Set to

(2 wire control; run/stop with reverse select)

2

F318

DI3 terminal function setting

Default is 15 ; set to

to select Run Fwd

15

F319

DI4 terminal function setting

Default is 16; set to

to select Run Rev

16

11.1 Parameters to change for remote Run/Stop

Two suitable 2 position NO (Normally Open)
switches should be installed: One between
terminals 24V and DI3 (Run / Stop) and the other
between terminals 24V and DI4 (Forward /
Reverse).

If the application only requires the motor to turn in
one direction, the Forward/Reverse switch can be
omitted.

When the NPN/PNP jumper is set to PNP (the
default), the 24V terminal is a common connection
for the digital terminals (terminals prefixed with
“D”). If you prefer to set the jumper to NPN, use CM
as the common instead.

Note that the Forward/Reverse switch only selects
the direction of rotation - it will not start or stop the
motor. The direction can be set either before the
motor is started or whilst it is running and is
indicated by the “FWD” lamp on the Inverter.

11.2 Connecting the Switches

A wiring diagram is shown in the illustration
opposite.

1

1

2

R

Switch, 2 Position

Normally Open

“Forward / Reverse”

Switch, 2 Position

Normally Open

“Run / Stop”

Parker AC10 Series Inverter (to 22kW)

3

NPN/PNP
switch “J7"

1

2 3

Summary of Contents for AC10 series

Page 1: ...a safety device All safety considerations including but not limited to Emergency Stop provision should be assessed separately and are outside the scope of this guide Parker AC10 Frequency Inverter to...

Page 2: ...nd configure a Potentiometer for remote speed control Contents Parameters Overview Parameters to set before use How to connect and configure a Run Stop switch with Forward Reverse selection Power and...

Page 3: ...tor phases determines the initial direction the motor turns Notes Important Use screened or armoured cable between the Inverter and Motor and ensure it is grounded as shown The supply must match the I...

Page 4: ...is not important They should be connected to the terminals marked L1 R L2 S and L3 T as shown In some cases these terminals may be marked L1 L2 and L3 only Notes The order of the three motor phases d...

Page 5: ...hanging from Delta to allow the motor to be changed back in future For safety purposes Star shown opposite is the default configuration for small motors usually to 3kW and is sometimes known as two at...

Page 6: ...power down 0 F228 Application Selection Defaults below are based on F228 0 Default is will suit most applications 5 different application Macros available 0 F801 Rated Motor Power kW Rated kW of the...

Page 7: ...roup mode the DGT digit lamp is not illuminated 6 2 Select the required parameter group Use the up and down keys to select parameter group F800 6 3 Select the required parameter Press the 0 stop key t...

Page 8: ...used to cycle through other values such as motor rpm current A and voltage U Parker AC10 Series Inverter to 22kW 7 1 Select the speed reference Press the M key repeatedly until the speed reference is...

Page 9: ...Motor Power kW Rated kW of the motor Set to match the motor nameplate eg 2 2kW 2200 F802 Rated Motor Voltage V Rated Voltage of the motor Set to match the motor nameplate eg V 230 F803 Rated Motor Cu...

Page 10: ...rated from 2kOhm to 5kOhm can be used eg 4 7kOhm The default output frequency at 0V is the minimum frequency of the Inverter To change this edit Parameter F112 The default output frequency at 10V is...

Page 11: ...on opposite When a connection is made between terminals 24V and DI3 the motor will run forward When terminals 24V and DI4 are connected the motor will run in reverse The selected direction of rotation...

Page 12: ...15 set to to select Run Fwd 15 F319 DI4 terminal function setting Default is 16 set to to select Run Rev 16 11 1 Parameters to change for remote Run Stop Two suitable 2 position NO Normally Open swit...

Page 13: ...rse Select Open Forward Closed Reverse 16 12 1 Parameters to change for remote 3 wire control Note that the Forward Reverse switch can be used to set the direction when the motor is stopped or running...

Page 14: ...or manual issued by the manufacturer for details 13 2 Connecting the Resistor The braking resistor may get hot during operation Ensure that it is suitably mounted so any heat generated will not affec...

Page 15: ...0 F800 etc Use the up and down keys to select parameter group F100 14 2 Select parameter group 1 Note In parameter group mode the DGT digit lamp is not illuminated Use the up and down keys to select p...

Reviews: