background image

 Magellan / Spectra SP

15

Zone Reporting Codes 

(Default = FF)

             

Refer to 

Decimal and Hexadecimal Values 

on page 49.                                                                                                                 

Section

Alarm

Alarm Restore

Tamper

Tamper Restore

[141]

Zone 1:

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[142]

Zone 2: 

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[143]

Zone 3:

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[144]

Zone 4: 

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[145]

Zone 5: 

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[146]

Zone 6: 

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[147]

Zone 7: 

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[148]

Zone 8: 

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[149]

Zone 9: 

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[150]

Zone 10:

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[151]

Zone 11: 

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[152]

Zone 12: 

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[153]

Zone 13: 

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[154]

Zone 14: 

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[155]

Zone 15: 

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[156]

Zone 16:

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[157]

Zone 17:

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[158]

Zone 18: 

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[159]

Zone 19:

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[160]

Zone 20: 

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[161]

Zone 21: 

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[162]

Zone 22: 

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[163]

Zone 23: 

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[164]

Zone 24: 

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[165]

Zone 25: 

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[166]

Zone 26:

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[167]

Zone 27: 

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[168]

Zone 28: 

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[169]

Zone 29: 

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[170]

Zone 30: 

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[171]

Zone 31: 

 _____/_____

 _____/_____

 _____/_____

 _____/_____

[172]

Zone 32:

 _____/_____

 _____/_____

 _____/_____

 _____/_____

Summary of Contents for SP5500

Page 1: ...hope this product performs to your complete satisfaction Should you have any questions or comments please visit www paradox com and send us your comments MG5000 V2 31 MG5050 V2 31 SP5500 V2 31 SP6000...

Page 2: ...17 910 and 911 To set the default code go to section 398 on page 24 and refer to section 701 option 1 on page 35 System Master Code Default 1234 123456 The System Master code can use any arming method...

Page 3: ...gned to partition 1 Goes to next available zone Notes Partition 2 status LEDs display the signal strength of the selected wireless zone 4 LEDs best signal 1 LED weak signal No LEDs hardwired panel key...

Page 4: ...nter 4 or 6 digit code Step Action Details 1 INSTALLER CODE flash MAINTENANCE CODE may also be used 2 3 9 4 PHONE ENTER Enter PC phone up to 32 digits and press ENTER To erase WinLoad phone panel ID a...

Page 5: ...3 PGM NUMBER MG32LRF MG32LED MG32LCD 2 digits 01 to 16 MG10LEDV H 1 digit 1 to 0 10 4 ENROLL OR ERASE PGM Wireless PGM Open close cover Hardwired PGM press ENTER To erase a PGM press the SLEEP key for...

Page 6: ...LED Keypad Module 15 total including APR ZX8 MG10LED Min 44mA Max 72mA MG32LED Min 49mA Max 148mA MG32LCD Min 43mA Max 86mA APR ZX8 8 Zone Expansion Module 3 Min 29mA Max 31mA MG RPT1 Magellan Wirele...

Page 7: ...Path Zone Entry Point Path Zone Path Zone Path Zone Keypad 1 APR ZX8 Keypad 2 APR ZX8 Keypad 3 APR ZX8 Keypad 4 APR ZX8 Keypad 5 APR ZX8 Keypad 6 APR ZX8 Keypad 7 APR ZX8 Keypad 8 APR ZX8 Keypad 9 AP...

Page 8: ...nning Serial Sticker Description Serial Sticker Description PGM 1 PGM 9 PGM 2 PGM 10 PGM 3 PGM 11 PGM 4 PGM 12 PGM 5 PGM 13 PGM 6 PGM 14 PGM 7 PGM 15 PGM 8 PGM 16 Serial Sticker Description Serial Sti...

Page 9: ...Stay Sleep Full Zone N N N Zone N N N Zone N N N Zone N N N Zone N N N Zone N N N Zone N N N Zone N N N Zone N N N Zone N N N Zone N N N Zone N N N Zone N N N Zone N N N Zone N N N Zone N N N Zone N N...

Page 10: ...tant 20 24Hr Water 21 24Hr Freeze 22 24hr Panic 23 Instant No Pre Alarm Flex Instant Zone will follow the delay at section 720 default is 15 seconds 0 instant zone 24 Follow No Pre Alarm On board hard...

Page 11: ...____ _____ 1 2 3 4 5 6 7 8 075 ____ ____ ____ ____ ____ ____ Zone 16 _________________________ 016 _____ _____ _____ 1 2 3 4 5 6 7 8 076 ____ ____ ____ ____ ____ ____ Zone 17 _________________________...

Page 12: ...Input 3B Zone 9 Input 7 Input 5 Input 4 Panel Input 4B Zone 10 Input 8 Input 6 Input 5 Panel Input 5B Zone 11 ZX8 B Input 1 Input 7 Input 6 ZX8 A Input 1 Zone 12 Input 2 Input 8 Input 7 Input 2 Zone 1...

Page 13: ...1 Input 3 Panel Input 3B Panel Input 11 Panel Input 11A Zone 12 Input 7 Input 2 Input 4 Panel Input 4B Panel Input 12 Panel Input 12A Zone 13 Input 8 Input 3 Input 5 Panel Input 5B Panel Input 13 Pane...

Page 14: ...____ ____ ____ 000 to 255 x 10ms Hardwire Zone 2 Speed 043 Zone 3 Z3 Z3 Z3 ____ ____ ____ 000 to 255 x 10ms Hardwire Zone 3 Speed 044 Zone 4 Z4 Z4 Z4 ____ ____ ____ 000 to 255 x 10ms Hardwire Zone 4 S...

Page 15: ...ne 14 _____ _____ _____ _____ _____ _____ _____ _____ 155 Zone 15 _____ _____ _____ _____ _____ _____ _____ _____ 156 Zone 16 _____ _____ _____ _____ _____ _____ _____ _____ 157 Zone 17 _____ _____ __...

Page 16: ...2 digits 01 to 32 MG10LEDV H 1 digit 1 to 0 10 To erase a keypad zone number press CLEAR then ENTER Step Action Details 1 ENTER INSTALLER CODE default 0000 000000 ARM STAY flash 2 Press and hold OFF 3...

Page 17: ...1 Deactivation Event ____ ____ ____ ____ ____ ____ 00 00 00 232 PGM 7 Activation Event ____ ____ ____ ____ ____ ____ 00 00 00 233 Deactivation Event ____ ____ ____ ____ ____ ____ 00 00 00 234 PGM 8 Ac...

Page 18: ...en armed in stay mode 07 PC fail to communicate Partition 1 only 08 Utility Key 1 pressed keys 1 and 2 Partition 1 only 09 Utility Key 2 pressed keys 2 and 3 Partition 1 only 10 Utility Key 3 pressed...

Page 19: ...NEware through GSM module 08 NEware through modem 09 IP100 direct 10 VDMP3 direct 11 VDMP3 through GSM module 27 Bus module event 00 A bus module was added 01 A bus module was removed 02 2 way RF Modu...

Page 20: ...communicate to monitoring station telephone 1 09 Fail to communicate to monitoring station telephone 2 10 Fail to communicate to pager report 11 Fail to communicate to voice report 12 RF interference...

Page 21: ...Wireless keypad 57 Non medical alarm paramedic 01 to 32 User number 99 Any user number 58 Zone forced 01 to 32 Zone number 99 Any zone number 59 Zone included Default Bold Section PGM 1 261 PGM 2 262...

Page 22: ...PGM 3 ___ ___ ___ 001 005 015 030 x 1 sec mins ___ ___ ___ 000 to 255 x 1 sec mins 284 PGM 4 ___ ___ ___ 001 005 015 030 x 1 sec mins ___ ___ ___ 000 to 255 x 1 sec mins 285 PGM 5 ___ ___ ___ 001 005...

Page 23: ..._ ____ ____ ____ 316 PGM 16 ____ ____ ____ ____ ____ ____ Section Section 321 PGM 1 Wireless PGM Signal Strength 329 PGM 9 Wireless PGM Signal Strength 322 PGM 2 Wireless PGM Signal Strength 330 PGM 1...

Page 24: ...he sections that the Maintenance Code cannot access 395 Installer code lock 816 Monitoring station telephone number 2 397 Installer code 817 Backup monitoring station telephone 398 Maintenance code 91...

Page 25: ...__ ____ 486 User 16 ____ ____ ____ ____ 502 User 32 ____ ____ ____ ____ Section Remote Serial Number Section Remote Serial Number 651 RC 1 for User 1 ____ ____ ____ ____ ____ ____ 667 RC 17 for User 1...

Page 26: ...636 26 ______ ______ ______ ______ 620 10 ______ ______ ______ ______ 637 27 ______ ______ ______ ______ 621 11 ______ ______ ______ ______ 638 28 ______ ______ ______ ______ 622 12 ______ ______ ___...

Page 27: ...d green slow flash Confirmation beep Exit delay Red on Confirmation beep Arming Entry Delay Red fast flash Alarm beep Alarm LED Sequence Auditory Sequence Action Green on Two beeps Disarming Yellow gr...

Page 28: ...3 beeps Best signal 5 to 7 2 beeps Average signal 1 to 4 1 beep Weak signal Relocate Default Bold Section MG RPT1 1 551 MG RPT1 2 561 Option OFF ON OFF ON 1 Repeat Wireless Keypad 1 Signals N N 2 Rep...

Page 29: ...at Wireless Zone 17 Signals N N 2 Repeat Wireless Zone 18 Signals N N 3 Repeat Wireless Zone 19 Signals N N 4 Repeat Wireless Zone 20 Signals N N 5 Repeat Wireless Zone 21 Signals N N 6 Repeat Wireles...

Page 30: ...N 6 Repeat Wireless 2 Way PGM 6 Signals N N 7 Repeat Wireless 2 Way PGM 7 Signals N N 8 Repeat Wireless 2 Way PGM 8 Signals N N Default Bold Section MG RPT1 1 557 MG RPT1 2 567 Option OFF ON OFF ON 1...

Page 31: ...2 ____ ____ ____ ____ ____ ____ 573 Keypad 3 ____ ____ ____ ____ ____ ____ 574 Keypad 4 ____ ____ ____ ____ ____ ____ 575 Keypad 5 ____ ____ ____ ____ ____ ____ 576 Keypad 6 ____ ____ ____ ____ ____...

Page 32: ...N Enabled 2 Keypad 2 Supervision N Disabled N Enabled 3 Keypad 3 Supervision N Disabled N Enabled 4 Keypad 4 Supervision N Disabled N Enabled 5 Keypad 5 Supervision N Disabled N Enabled 6 Keypad 6 Sup...

Page 33: ...__ __ 202 22 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ 187 7 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ 203 23 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ 188 8 __ __ __ __ __ __ __ __...

Page 34: ...__ __ __ __ __ __ __ __ __ __ __ __ 530 20 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ 515 5 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ 531 21 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __...

Page 35: ...M2 V2 01 or higher 7 Display entry delay on LCD keypad MG32LCD N Disabled N Enabled 8 Display exit delay on LCD keypad MG32LCD N Disabled N Enabled 702 Panic Options Bold Default setting Option OFF ON...

Page 36: ...Zone Options 2 Bold Default setting Option OFF ON 1 Check in supervision time N 24 hours N 80 minutes 2 EOL resistors N Disabled N Enabled 3 Zone Input 1 becomes a 2 wire smoke input except SP5500 N D...

Page 37: ...000 to 255 seconds Remote panic disarm lock delay default 000 719 ____ ____ ____ 000 to 255 days Closing delinquency delay default 000 720 ____ ____ ____ 000 to 255 seconds For StayD Flex Instant del...

Page 38: ...is opened N Disabled N Enabled 6 Follow zones become entry delay 2 when delay zone is bypassed N Disabled N Enabled 7 8 N A N A N A Section Data Description 745 ____ ____ ____ 000 to 255 seconds Parti...

Page 39: ...7 Call pager for alarm restore reporting codes N Disabled N Enabled 8 N A N A N A Telephone Line Monitoring TLM Options 1 2 OFF OFF Disabled OFF ON When disarmed Trouble only When armed Trouble only O...

Page 40: ...6 Call personal tel on panic alarms N Disabled N Enabled 7 Call personal tel on parademic alarm N Disabled N Enabled 8 N A N A N A Section Data Description 810 ___ ___ Reporting format TEL1 TEL2 0 Ade...

Page 41: ...max 127 Pager reporting delay default 020 835 ____ ____ ____ 000 to 255 max 10 Pager reporting message repetition default 003 836 ____ ____ ____ 000 to 255 sec max 127 Personal reporting delay defaul...

Page 42: ...____ Cancel auto arm _____ _____ Disarming via PC _____ _____ Cancel alarm with user or WinLoad _____ _____ Cancel parademic Section Data Description Section Data Description 863 _____ _____ Emergency...

Page 43: ...unicate ____ ____ RF interference ____ ____ Module lost ____ ____ Module tamper Section Data Description Section Data Description 870 ____ ____ TLM 873 ____ ____ Module power fail ____ ____ AC failure...

Page 44: ...N Disabled N Enabled Enable all options you want to reset to default The respective sets of reporting codes will be reset to default after exiting the section 900 WinLoad Options Bold Default setting...

Page 45: ...352 Telco 2 fault 5F 125 Duress Egress granted 12 System Troubles 300 and 310 353 Long range radio 60 Burglar Alarms 130 300 System trouble 39 354 Fail to communicate 61 130 Burglary 13 301 AC loss 3...

Page 46: ...626 Time Date inaccurate D1 412 Success download access 84 522 Bell 2 disabled AB 627 Program mode entry D2 413 Unsuccessful access 85 523 Alarm relay disabled AC 628 Program mode exit D3 414 System...

Page 47: ...ary alarm restore Fire alarm restore 3 11A Fire alarm restore FH Fire alarm restore Panic 1 emergency 1 12A Panic alarm PA Panic alarm Panic 2 medical 1 1AA Medical alarm MA Medical alarm Panic 3 fire...

Page 48: ...1 627 Program mode entry LB Local program Maintenance out 1 628 Program mode exit LS Local program success Closing delinquency 1 654 System inactivity CD System inactivity Module AC fail 1 342 AC fail...

Page 49: ...set all eight options to OFF When the options are set press the ENTER key to save and advance to the next section Decimal and Hexadecimal Values Value or Action What Do I Press What Do I See 32 zone...

Page 50: ...le Sub Menu Trouble Menu 1 Wireless zone low battery 1 to 32 Zones in low battery 2 Power trouble 1 Low No battery on the control panel 2 AC failure on control panel 3 Auxiliary overload on control pa...

Page 51: ...Magellan Spectra SP 51 Hardware Connections Single Zone Inputs...

Page 52: ...52 Programming Guide Advanced Technology Zone ATZ Connections...

Page 53: ...ation Program the Activation Event so that the smoke detectors can be reset by pressing the CLEAR ENTER keys for three seconds See Event Group 6 on page 18 For 2 wire installation except SP5500 Press...

Page 54: ...the Com port settings button and select the correct Com port Then click the Refresh Product Info button to connect with the panel 5 To check for new updates click the Download Firmware from the web b...

Page 55: ...d dotted line represent the mounting location If you need specific dimensions contact Paradox Distributor Support For UL recommended installation for the MG5000 only place the PCB one notch lower than...

Page 56: ...56 Programming Guide SP5500 8x10 SP6000 11x11 SP7000 11x11...

Page 57: ...ss over the antennae as this may affect signal reception Paradox Memory Key PMC 3 PMC 4 Antennas RX TX LED Flashes quickly when receiving or transmitting RF signals from wireless devices STATUS LED Fl...

Page 58: ...tance of keypad from panel 76m 250 feet Max total run of wire 230m 750 feet Disconnect telephone line before servicing AUX Power Refer to transformer requirements on page 53 for Aux Power Output To co...

Page 59: ...d AUX must be limited to 1 3A 40VA transformer strongly recommended Exceeding this limit will overload the panel power supply and lead to complete system shutdown Connection for Self Contained Bell Si...

Page 60: ...r to the UL and C UL Warnings section at the back of the Reference Installation Manual The sum of the current drawn from the BELL and AUX must be limited to 1 3A 40VA transformer strongly recommended...

Page 61: ...el only For UL and C UL warnings refer to the UL and C UL Warnings section at the back of the Reference Installation Manual The sum of the current drawn from the BELL and AUX must be limited to 1 3A 4...

Page 62: ...elines when configuring the system All components of the system should be UL listed for the intended application If used for Fire detection the installer should refer to NFPA Standards 72 Chapter 2 In...

Page 63: ......

Page 64: ...paradox com Printed in Canada 07 2007 MGSP EP11...

Reviews: