Programming Guide

387 Intrusion detector Hi 

sensitivity

75

451 Early open/close

9A

603 Periodic RF transmission

BF

388 Intrusion detector Low 

sensitivity

76

452 Late open/close

9B

604 Fire test

C0

389 Sensor self-test failure

77

453 Failed to open

9C

605 Status report to follow

C1

391 Sensor watch trouble

78

454 Failed to close

9D

606 Listen-in to follow

C2

392 Drift compensation error

79

455 Auto-arm failed

9E

607 Walk test mode

C3

393 Maintenance alert

7A

456 Partial arm

9F

608 Periodic test - system 

trouble present

C4

Open/Close - 400

457 Exit error (user)

A0

609 Video transmitter active

C5

400 Open/Close

7B

458 User on premises

A1

611 Point test OK

C6

401 Open/Close by user

7C

459 Recent close

A2

612 Point not tested

C7

402 Group open/close

7D

System - 460

613 Intrusion zone walk tested

C8

403 Automatic open/close

7E

461 Wrong code entry

A3

614 Fire zone walk tested

C9

462 Legal code entry

A4

615 Panic zone walk tested

CA

463 Re-arm after alarm

A5

616 Service request

CB

406 Cancel

7F

464 Auto-arm time extended

A6

621 Event log reset

CC

407 Remote arm/disarm

80

465 Panic alarm reset

A7

622 Event log 50% full

CD

408 Quick arm

81

466 Service ON/OFF premises

A8

623 Event log 90% full

CE

409 Keyswitch open/close

82

Sounder Relay Disabled - 520

624 Event log overflow

CF

Remote Access - 410

520 Sounder/Relay disabled

A9

625 Time/Date reset

D0

411 Call back request made

83

521 Bell 1 disabled

AA

626 Time/Date inaccurate

D1

412 Success - download 

access

84

522 Bell 2 disabled

AB

627 Program mode entry

D2

413 Unsuccessful access

85

523 Alarm relay disabled

AC

628 Program mode exit

D3

414 System shutdown

86

524 Trouble relay disabled

AD

629 32-hour event log marker

D4

415 Dialer shutdown

87

525 Reversing relay disabled

AE

630 Schedule change

D5

416 Successful upload

88

526 Notification appliance chk. 

#3 disabled

AF

631 Exception schedule 

change

D6

Access Control - 420 and 430

527 Notification appliance chk. 

#4 disabled

B0

632 Access schedule change

D7

421 Access denied

89

Modules - 530

654 System inactivity

D8

422 Access report by user

8A

531 Module added

B1

423 Forced access

8B

532 Module removed

B2

424 Egress denied

8C

Communication Disables - 550 and 560

425 Egress granted

8D

551 Dialer disabled

B3

426 Access door propped open

8E

552 Radio transmitter disabled

B4

427 Access point door status 

monitor trouble

8F

Bypasses - 570

428

Access point request to exit

90

570 Zone bypass

B5

429

Access program mode entry

91

571 Fire bypass

B6

430 Access program mode exit

92

572 24Hr. zone bypass

B7

431 Access threat level change

93

573 Burglary bypass

B8

432 Access relay/trigger fail

94

574 Group bypass

B9

433 Access RTE shunt

95

575 Swinger bypass

BA

434 Access DSM shunt

96

576 Access zone shunt

BB

Arming - 440 and 450

577 Access point bypass

BC

441 Armed Stay

97

Test/Misc. - 600

442 Keyswitch armed Stay

98

601 Manual trigger test

BD

450 Exception open/close

99

602 Periodic test report

BE

CID#

Reporting Code

Programming 
Value

CID#

Reporting Code

Programming 
Value

CID#

Reporting Code

Program-
ming Value

Summary of Contents for SP5500

Page 1: ...hope this product performs to your complete satisfaction Should you have any questions or comments please visit www paradox com and send us your comments MG5000 V2 31 MG5050 V2 31 SP5500 V2 31 SP6000...

Page 2: ...17 910 and 911 To set the default code go to section 398 on page 24 and refer to section 701 option 1 on page 35 System Master Code Default 1234 123456 The System Master code can use any arming method...

Page 3: ...gned to partition 1 Goes to next available zone Notes Partition 2 status LEDs display the signal strength of the selected wireless zone 4 LEDs best signal 1 LED weak signal No LEDs hardwired panel key...

Page 4: ...nter 4 or 6 digit code Step Action Details 1 INSTALLER CODE flash MAINTENANCE CODE may also be used 2 3 9 4 PHONE ENTER Enter PC phone up to 32 digits and press ENTER To erase WinLoad phone panel ID a...

Page 5: ...3 PGM NUMBER MG32LRF MG32LED MG32LCD 2 digits 01 to 16 MG10LEDV H 1 digit 1 to 0 10 4 ENROLL OR ERASE PGM Wireless PGM Open close cover Hardwired PGM press ENTER To erase a PGM press the SLEEP key for...

Page 6: ...LED Keypad Module 15 total including APR ZX8 MG10LED Min 44mA Max 72mA MG32LED Min 49mA Max 148mA MG32LCD Min 43mA Max 86mA APR ZX8 8 Zone Expansion Module 3 Min 29mA Max 31mA MG RPT1 Magellan Wirele...

Page 7: ...Path Zone Entry Point Path Zone Path Zone Path Zone Keypad 1 APR ZX8 Keypad 2 APR ZX8 Keypad 3 APR ZX8 Keypad 4 APR ZX8 Keypad 5 APR ZX8 Keypad 6 APR ZX8 Keypad 7 APR ZX8 Keypad 8 APR ZX8 Keypad 9 AP...

Page 8: ...nning Serial Sticker Description Serial Sticker Description PGM 1 PGM 9 PGM 2 PGM 10 PGM 3 PGM 11 PGM 4 PGM 12 PGM 5 PGM 13 PGM 6 PGM 14 PGM 7 PGM 15 PGM 8 PGM 16 Serial Sticker Description Serial Sti...

Page 9: ...Stay Sleep Full Zone N N N Zone N N N Zone N N N Zone N N N Zone N N N Zone N N N Zone N N N Zone N N N Zone N N N Zone N N N Zone N N N Zone N N N Zone N N N Zone N N N Zone N N N Zone N N N Zone N N...

Page 10: ...tant 20 24Hr Water 21 24Hr Freeze 22 24hr Panic 23 Instant No Pre Alarm Flex Instant Zone will follow the delay at section 720 default is 15 seconds 0 instant zone 24 Follow No Pre Alarm On board hard...

Page 11: ...____ _____ 1 2 3 4 5 6 7 8 075 ____ ____ ____ ____ ____ ____ Zone 16 _________________________ 016 _____ _____ _____ 1 2 3 4 5 6 7 8 076 ____ ____ ____ ____ ____ ____ Zone 17 _________________________...

Page 12: ...Input 3B Zone 9 Input 7 Input 5 Input 4 Panel Input 4B Zone 10 Input 8 Input 6 Input 5 Panel Input 5B Zone 11 ZX8 B Input 1 Input 7 Input 6 ZX8 A Input 1 Zone 12 Input 2 Input 8 Input 7 Input 2 Zone 1...

Page 13: ...1 Input 3 Panel Input 3B Panel Input 11 Panel Input 11A Zone 12 Input 7 Input 2 Input 4 Panel Input 4B Panel Input 12 Panel Input 12A Zone 13 Input 8 Input 3 Input 5 Panel Input 5B Panel Input 13 Pane...

Page 14: ...____ ____ ____ 000 to 255 x 10ms Hardwire Zone 2 Speed 043 Zone 3 Z3 Z3 Z3 ____ ____ ____ 000 to 255 x 10ms Hardwire Zone 3 Speed 044 Zone 4 Z4 Z4 Z4 ____ ____ ____ 000 to 255 x 10ms Hardwire Zone 4 S...

Page 15: ...ne 14 _____ _____ _____ _____ _____ _____ _____ _____ 155 Zone 15 _____ _____ _____ _____ _____ _____ _____ _____ 156 Zone 16 _____ _____ _____ _____ _____ _____ _____ _____ 157 Zone 17 _____ _____ __...

Page 16: ...2 digits 01 to 32 MG10LEDV H 1 digit 1 to 0 10 To erase a keypad zone number press CLEAR then ENTER Step Action Details 1 ENTER INSTALLER CODE default 0000 000000 ARM STAY flash 2 Press and hold OFF 3...

Page 17: ...1 Deactivation Event ____ ____ ____ ____ ____ ____ 00 00 00 232 PGM 7 Activation Event ____ ____ ____ ____ ____ ____ 00 00 00 233 Deactivation Event ____ ____ ____ ____ ____ ____ 00 00 00 234 PGM 8 Ac...

Page 18: ...en armed in stay mode 07 PC fail to communicate Partition 1 only 08 Utility Key 1 pressed keys 1 and 2 Partition 1 only 09 Utility Key 2 pressed keys 2 and 3 Partition 1 only 10 Utility Key 3 pressed...

Page 19: ...NEware through GSM module 08 NEware through modem 09 IP100 direct 10 VDMP3 direct 11 VDMP3 through GSM module 27 Bus module event 00 A bus module was added 01 A bus module was removed 02 2 way RF Modu...

Page 20: ...communicate to monitoring station telephone 1 09 Fail to communicate to monitoring station telephone 2 10 Fail to communicate to pager report 11 Fail to communicate to voice report 12 RF interference...

Page 21: ...Wireless keypad 57 Non medical alarm paramedic 01 to 32 User number 99 Any user number 58 Zone forced 01 to 32 Zone number 99 Any zone number 59 Zone included Default Bold Section PGM 1 261 PGM 2 262...

Page 22: ...PGM 3 ___ ___ ___ 001 005 015 030 x 1 sec mins ___ ___ ___ 000 to 255 x 1 sec mins 284 PGM 4 ___ ___ ___ 001 005 015 030 x 1 sec mins ___ ___ ___ 000 to 255 x 1 sec mins 285 PGM 5 ___ ___ ___ 001 005...

Page 23: ..._ ____ ____ ____ 316 PGM 16 ____ ____ ____ ____ ____ ____ Section Section 321 PGM 1 Wireless PGM Signal Strength 329 PGM 9 Wireless PGM Signal Strength 322 PGM 2 Wireless PGM Signal Strength 330 PGM 1...

Page 24: ...he sections that the Maintenance Code cannot access 395 Installer code lock 816 Monitoring station telephone number 2 397 Installer code 817 Backup monitoring station telephone 398 Maintenance code 91...

Page 25: ...__ ____ 486 User 16 ____ ____ ____ ____ 502 User 32 ____ ____ ____ ____ Section Remote Serial Number Section Remote Serial Number 651 RC 1 for User 1 ____ ____ ____ ____ ____ ____ 667 RC 17 for User 1...

Page 26: ...636 26 ______ ______ ______ ______ 620 10 ______ ______ ______ ______ 637 27 ______ ______ ______ ______ 621 11 ______ ______ ______ ______ 638 28 ______ ______ ______ ______ 622 12 ______ ______ ___...

Page 27: ...d green slow flash Confirmation beep Exit delay Red on Confirmation beep Arming Entry Delay Red fast flash Alarm beep Alarm LED Sequence Auditory Sequence Action Green on Two beeps Disarming Yellow gr...

Page 28: ...3 beeps Best signal 5 to 7 2 beeps Average signal 1 to 4 1 beep Weak signal Relocate Default Bold Section MG RPT1 1 551 MG RPT1 2 561 Option OFF ON OFF ON 1 Repeat Wireless Keypad 1 Signals N N 2 Rep...

Page 29: ...at Wireless Zone 17 Signals N N 2 Repeat Wireless Zone 18 Signals N N 3 Repeat Wireless Zone 19 Signals N N 4 Repeat Wireless Zone 20 Signals N N 5 Repeat Wireless Zone 21 Signals N N 6 Repeat Wireles...

Page 30: ...N 6 Repeat Wireless 2 Way PGM 6 Signals N N 7 Repeat Wireless 2 Way PGM 7 Signals N N 8 Repeat Wireless 2 Way PGM 8 Signals N N Default Bold Section MG RPT1 1 557 MG RPT1 2 567 Option OFF ON OFF ON 1...

Page 31: ...2 ____ ____ ____ ____ ____ ____ 573 Keypad 3 ____ ____ ____ ____ ____ ____ 574 Keypad 4 ____ ____ ____ ____ ____ ____ 575 Keypad 5 ____ ____ ____ ____ ____ ____ 576 Keypad 6 ____ ____ ____ ____ ____...

Page 32: ...N Enabled 2 Keypad 2 Supervision N Disabled N Enabled 3 Keypad 3 Supervision N Disabled N Enabled 4 Keypad 4 Supervision N Disabled N Enabled 5 Keypad 5 Supervision N Disabled N Enabled 6 Keypad 6 Sup...

Page 33: ...__ __ 202 22 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ 187 7 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ 203 23 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ 188 8 __ __ __ __ __ __ __ __...

Page 34: ...__ __ __ __ __ __ __ __ __ __ __ __ 530 20 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ 515 5 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ 531 21 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __...

Page 35: ...M2 V2 01 or higher 7 Display entry delay on LCD keypad MG32LCD N Disabled N Enabled 8 Display exit delay on LCD keypad MG32LCD N Disabled N Enabled 702 Panic Options Bold Default setting Option OFF ON...

Page 36: ...Zone Options 2 Bold Default setting Option OFF ON 1 Check in supervision time N 24 hours N 80 minutes 2 EOL resistors N Disabled N Enabled 3 Zone Input 1 becomes a 2 wire smoke input except SP5500 N D...

Page 37: ...000 to 255 seconds Remote panic disarm lock delay default 000 719 ____ ____ ____ 000 to 255 days Closing delinquency delay default 000 720 ____ ____ ____ 000 to 255 seconds For StayD Flex Instant del...

Page 38: ...is opened N Disabled N Enabled 6 Follow zones become entry delay 2 when delay zone is bypassed N Disabled N Enabled 7 8 N A N A N A Section Data Description 745 ____ ____ ____ 000 to 255 seconds Parti...

Page 39: ...7 Call pager for alarm restore reporting codes N Disabled N Enabled 8 N A N A N A Telephone Line Monitoring TLM Options 1 2 OFF OFF Disabled OFF ON When disarmed Trouble only When armed Trouble only O...

Page 40: ...6 Call personal tel on panic alarms N Disabled N Enabled 7 Call personal tel on parademic alarm N Disabled N Enabled 8 N A N A N A Section Data Description 810 ___ ___ Reporting format TEL1 TEL2 0 Ade...

Page 41: ...max 127 Pager reporting delay default 020 835 ____ ____ ____ 000 to 255 max 10 Pager reporting message repetition default 003 836 ____ ____ ____ 000 to 255 sec max 127 Personal reporting delay defaul...

Page 42: ...____ Cancel auto arm _____ _____ Disarming via PC _____ _____ Cancel alarm with user or WinLoad _____ _____ Cancel parademic Section Data Description Section Data Description 863 _____ _____ Emergency...

Page 43: ...unicate ____ ____ RF interference ____ ____ Module lost ____ ____ Module tamper Section Data Description Section Data Description 870 ____ ____ TLM 873 ____ ____ Module power fail ____ ____ AC failure...

Page 44: ...N Disabled N Enabled Enable all options you want to reset to default The respective sets of reporting codes will be reset to default after exiting the section 900 WinLoad Options Bold Default setting...

Page 45: ...352 Telco 2 fault 5F 125 Duress Egress granted 12 System Troubles 300 and 310 353 Long range radio 60 Burglar Alarms 130 300 System trouble 39 354 Fail to communicate 61 130 Burglary 13 301 AC loss 3...

Page 46: ...626 Time Date inaccurate D1 412 Success download access 84 522 Bell 2 disabled AB 627 Program mode entry D2 413 Unsuccessful access 85 523 Alarm relay disabled AC 628 Program mode exit D3 414 System...

Page 47: ...ary alarm restore Fire alarm restore 3 11A Fire alarm restore FH Fire alarm restore Panic 1 emergency 1 12A Panic alarm PA Panic alarm Panic 2 medical 1 1AA Medical alarm MA Medical alarm Panic 3 fire...

Page 48: ...1 627 Program mode entry LB Local program Maintenance out 1 628 Program mode exit LS Local program success Closing delinquency 1 654 System inactivity CD System inactivity Module AC fail 1 342 AC fail...

Page 49: ...set all eight options to OFF When the options are set press the ENTER key to save and advance to the next section Decimal and Hexadecimal Values Value or Action What Do I Press What Do I See 32 zone...

Page 50: ...le Sub Menu Trouble Menu 1 Wireless zone low battery 1 to 32 Zones in low battery 2 Power trouble 1 Low No battery on the control panel 2 AC failure on control panel 3 Auxiliary overload on control pa...

Page 51: ...Magellan Spectra SP 51 Hardware Connections Single Zone Inputs...

Page 52: ...52 Programming Guide Advanced Technology Zone ATZ Connections...

Page 53: ...ation Program the Activation Event so that the smoke detectors can be reset by pressing the CLEAR ENTER keys for three seconds See Event Group 6 on page 18 For 2 wire installation except SP5500 Press...

Page 54: ...the Com port settings button and select the correct Com port Then click the Refresh Product Info button to connect with the panel 5 To check for new updates click the Download Firmware from the web b...

Page 55: ...d dotted line represent the mounting location If you need specific dimensions contact Paradox Distributor Support For UL recommended installation for the MG5000 only place the PCB one notch lower than...

Page 56: ...56 Programming Guide SP5500 8x10 SP6000 11x11 SP7000 11x11...

Page 57: ...ss over the antennae as this may affect signal reception Paradox Memory Key PMC 3 PMC 4 Antennas RX TX LED Flashes quickly when receiving or transmitting RF signals from wireless devices STATUS LED Fl...

Page 58: ...tance of keypad from panel 76m 250 feet Max total run of wire 230m 750 feet Disconnect telephone line before servicing AUX Power Refer to transformer requirements on page 53 for Aux Power Output To co...

Page 59: ...d AUX must be limited to 1 3A 40VA transformer strongly recommended Exceeding this limit will overload the panel power supply and lead to complete system shutdown Connection for Self Contained Bell Si...

Page 60: ...r to the UL and C UL Warnings section at the back of the Reference Installation Manual The sum of the current drawn from the BELL and AUX must be limited to 1 3A 40VA transformer strongly recommended...

Page 61: ...el only For UL and C UL warnings refer to the UL and C UL Warnings section at the back of the Reference Installation Manual The sum of the current drawn from the BELL and AUX must be limited to 1 3A 4...

Page 62: ...elines when configuring the system All components of the system should be UL listed for the intended application If used for Fire detection the installer should refer to NFPA Standards 72 Chapter 2 In...

Page 63: ......

Page 64: ...paradox com Printed in Canada 07 2007 MGSP EP11...

Reviews: