CABINET SENSOR HARDWARE INSTALLATION
MANUAL
51
Inspecting the Installation
Inspections ensure appropriate sensor placement, cable routing, and a clean installation
area.
1. Verify cabinet cable assembly placement.
•
Cabinet doors open wide without pulling cables backwards or forwards through the cabinet
•
All cables are taut, loose cables are secured with clips and cable ties as needed
•
Ensure enough slack in cabling prevents rubbing or chafing against sharp edges
•
Verify the connecting cable between the intake and exhaust sensor assemblies is correct (across
the top exterior of cabinets or inside across the ceiling of cabinets)
•
Sensors are in the path of intake and exhaust airflow
•
All sensors are straight and height is consistent between cabinets
•
Sensor placement is in the intake airflow path (and exhaust if needed)
•
Cable ties and clips do not interfere with fans or bind or rub against surfaces
2. Clear the installation area.
•
Remove all debris and tools from the data center floor and cabinets (inside and top)
•
Replace all floor tiles and close all cabinet doors
•
Properly dispose of all packaging, snipped cable tie ends, etc.