CABINET SENSOR HARDWARE INSTALLATION
MANUAL
26
Inspecting the Installation
Inspect the installation to ensure appropriate sensor placement and a clean installation
area.
1. Verify sensor placement.
•
All sensors are positioned consistently between cabinets
•
Sensor placement is in the intake and exhaust (as needed) airflow path
•
Cable ties and clips do not interfere with fans or bind or rub against surfaces
2. Clear the installation area.
•
Remove all debris and tools from the data center floor and cabinets (inside and
top)
•
Replace all floor tiles and close all cabinet doors
•
Properly dispose of all debris packaging, snipped cable tie ends, etc.