CABINET SENSOR HARDWARE INSTALLATION
MANUAL
23
Validating and Commissioning the ThermaNode
EZ
Validate and commission the ThermaNode EZ installation by checking sensor node
operation and communication with the SynapSense Web Console software application.
Refer to the Web Console User Guide for detailed information.
1. Verify all necessary installation activities (software installation, file exports, etc.) are
complete.
2. Assure all peripheral hardware / software is powered on and functional (gateway,
server, etc.).
3. Press and hold the ON/OFF button for two seconds to activate the node
4. Ensure LED light sequence initiates correctly (see the
following section
, Page 25).
5. Confirm sensor node operation and communication.
a. Open Web Console, select the data center from the
Sites
list.
b. Click the
Data View
tab and select
Nodes
from the
Data
View
dropdown menu. Cabinet Node data displays.
c. Verify green checks
for each installed node in the
Status
column.
•
A red “
X
” in the
Input
columns indicates a problem. Ensure the node is ON, and
check for loose connections or damaged wires.
•
Turn node off and on, allowing at least 15-20 minutes to rejoin the network.
d. Correct any errors and repeat the previous steps for software validation.