CABINET SENSOR HARDWARE INSTALLATION
MANUAL
46
5. Install node side (intake) sensor cable assembly using cable ties to attach the
top,
middle, and bottom sensors
. Ensure sensors point up and cable ties encircle
cable and sensors.
a. Install the top intake sensor along
the door centerline and secure with
a cable tie two-three inches from the
ThermaNode.
b. Install middle intake sensor in line
and under the top intake sensor.
c. Install the bottom intake sensor,
pointing up or down as cable length
allows, under middle intake sensor.
d. Secure cable above and below each
sensor with cable ties.
e. Pull extra cable in a loop beneath
sensor and cable tie at the lowest
point on the mesh.
f. Loop excess cable hanging and
cable tie at the lowest point to the
mesh.
g. Use adhesive-backed cable clips to
secure extra cable lengths.
h. Leave ample cable and loops where
cable spans door hinges to prevent
cable pulling or pinching when
opening and closing cabinet doors.
6. Route and secure the non-node (intake)
side cable assembly.
a. Install a cable clip on the non-node side
doorframe near the door hinge.
b. Route the cabling to the cable clip and
secure by wrapping around the post.
c. Ensure there is enough slack to form a
sufficient door hinge loop.
d. Secure intake sensor cable to cabinet
door mesh using cable ties (in two
places – see above).