![Panduit Synapsense ThermaNode EZ Installation Manual Download Page 40](http://html1.mh-extra.com/html/panduit/synapsense-thermanode-ez/synapsense-thermanode-ez_installation-manual_3444372040.webp)
CABINET SENSOR HARDWARE INSTALLATION
MANUAL
39
Open Frame Cabinets
Installing the ThermaNode
Mount the ThermaNode with adhesive strips on open frame (no door) cabinets:
1. Attach adhesive strips to the back of
ThermaNode (if not already present).
2. Clean area and allow area to dry thoroughly.
3. Plug cable assembly into the ThermaNode
connector.
4. Place cable assembly on top of cabinet to
prevent strain on the ThermaNode connector
during installation.
5. Remove adhesive covers from the strips and
install the ThermaNode and top sensor on the
upper-left portion of the cabinet frame, close to
the airflow.
6. Press in place for 30 seconds to ensure a
secure bond.
7. Secure cable assembly wiring (disconnects) for
intake and exhaust sensors with cable clips on
both sides of the ThermaNode to prevent strain
on the connector.
Installing Intake Sensors
1. Mount sensors with adhesive backed
sensor clips to the cabinet left-front
vertical frame at the top, middle and
bottom of the cabinet.
2. Secure extra cable lengths using
adhesive-backed cable clips and wrap
around post.
3. Pull cable loops taut and secure cables
together using cable ties as needed.
4. Install sensors inside the cabinet front
opening in the airflow path.
5. Install a cable clip and bundle extra wiring
by wrapping it around the post.
NOTE:
If excess cable is hanging 2 inches or