![Panduit smartzone U01N11L Installation Manual Download Page 67](http://html1.mh-extra.com/html/panduit/smartzone-u01n11l/smartzone-u01n11l_installation-manual_3603814067.webp)
SMARTZONE UPS INSTALLATION MANUAL
66
Input
Output
3
3
380/400/415 VAC
380/400/415 VAC
26.9 A each phase
15.2 A each phase
40 A each phase
not required
10 mm
2
6 mm
2
U15N32V
Input
Output
3
1
380/400/415 VAC
220/230/240 VAC
34.9 A each phase
68.2 A
100 A**
not required
25 mm
2
**
16 mm
2
Input
Output
3
3
380/400/415 VAC
380/400/415 VAC
34.9 A each phase
22.8 A each phase
40 A each phase
not required
10 mm
2
6 mm
2
U20N32V
Input
Output
3
1
380/400/415 VAC
220/230/240 VAC
42.9 A each phase
90.9 A
125 A**
not required
35 mm
2
**
25 mm
2
Input
Output
3
3
380/400/415 VAC
380/400/415 VAC
42.9 A each phase
30.4 A each phase
50 A each phase
not required
16 mm
2
10 mm
2
Wire Specification of Power Cables for Dual Feed
SKU
Wiring
Number
of
Phases
Voltage
Current
Full
Load***
(maximum)
External
Input
Circuit
Breaker
Mains
(typical)
External Input
Circuit
Breaker
Bypass
(typical)
Wire
Size
Mains*
(typical)
Wire
Size
Bypass*
(typical)
U10N32V
Input
Output
3
1
380/400/415
VAC
220/230/240
VAC
26.9 A each
phase
45.5 A
40 A each
phase
Not required
100 A **
not required
10 mm
2
16 mm
2
25 mm
2
**
16 mm
2
Input
Output
3
3
380/400/415
VAC
380/400/415
VAC
26.9 A each
phase
15.2 A each
phase
40 A each
phase
Not required
40 A each
phase
not required
10 mm
2
6 mm
2
10 mm
2
6 mm
2
U15N32V
Input
Output
3
1
380/400/415
VAC
220/230/240
VAC
34.9 A each
phase
68.2 A
40 A each
phase
Not required
100 A **
not required
10 mm
2
16 mm
2
25 mm
2
**
16 mm
2