15/05/96
18
MPC2000 01/96B
If the value of a parameter is changed but not stored and the display is scrolled to another page the parameter value
will be returned to the value stored in the EEPROM memory.
Note: It is possible to adjust and store setting parameters at any time , even whilst the motor is running. Changing the
value of a displayed parameter has no effect on the operation of the units until the STORE key is pressed.
After setting parameters have been stored to the EEP ROM memory they are kept indefinitely, this feature does not rely
on a battery backup system.
Reset Key
This key enables the operator to reset MPC2000 Fault or Alarm conditions. Pressing of this key can only perform a
reset if the following condition are met:
1 The Tripping/ Alarm Options for the specific fault or alarm re set to allow panel resets.
2. The condition that caused the Fault or Alarm to occur no longer exists
Providing condition 2 is met an operator can override the settings in the Tripping/Alarm Options by closing the
Authorize input and pressing the reset button. Note if the reset key is pressed and the Authorized input is closed a
flash message 'RESET THERMAL CAPACITY' is displayed and if the RESET button is pressed again whilst the
message is displayed the level of Thermal Capacity will be reset to zero.
Test Key
The pressing of this key will cause the unit to display the Test/Maintenance menu. Using the LINE DOWN/LINE
BACK keys the following options are displayed
Run Self Test
Program Version
Store Enable Default Settings
Reset Statistical Data
For instructions on the use of these options refer to the Test Maintenance Options section later in this manual
9. MPC2000 Setting And Data Pages
9.1. MPC2000 Communication Settings
Drive Number
This setting range 0-320 with a default setting of 0, identifies the MPC2000 by an overall system number . This does
not affect the communications which uses the Serial Link Number.
Baud Rate
This setting range 110,300,1200,4800,9600 Bits/Second with a default setting of 9600, determines the speed of
communications between the XCELL or when directly connected the Host system and the MPC2000. This is normally
set to the highest speed 9600 Bits/Second.
Serial Link No.
This setting range 1-33 with a default setting of 33, identifies the MPC2000 unit to the XCELL unit to which the RS485
Data Highway is connected, and is also required to be set if the MPCSET software is to be used .
Common Address 1,2 & 3
These settings are included for future developments and have no function at present.