15/05/96
29
MPC2000 01/96B
CURRENT SETTINGS
Maximum Start Time
1-250 Sec
10 Sec
Number of starts
1-10
10
Start Period
1-60 Min
30 Min
Start Inhibit Time
1-60 Min
30 Min
Undercurrent Alarm
10-90% FLC
50%
Undercurrent Alarm Delay
1-60 Sec
2 Sec
Undercurrent Trip
10-90% FLC
40$
Undercurrent Trip Delay
1-60 Sec
5 Sec
Load Increase Alarm
60-150% FLC
120%
Low Set Overcurrent
100-500% FLC
400%
Low Set Overcurrent Delay
0.5-10 Sec
2.0 Sec
High Set Overcurrent
400-1200% FLC
800%
High Set Overcurrent Delay
Inst-4 Sec
Inst
Overload Setting
60-130% FLC
105%
Thermal Capacity Alarm
50-99%
80%
t6x Time
0.5-120 Sec
10 Sec
Hot/Cold Ratio
20-100%
50%
Cool Time Factor
1-15
5
Stall Time Factor
20-100%
50
Overload reset Method
Auto,Hand
Hand
Unbalance Current
10-40%
15%
Current Unbalance Maximum Time
20-120 Sec
30 Sec
COMMUNICATION SETTINGS
Drive Number
1 - 320
0
Baud Rate
110,300,1200,2400,4800,9600
9600
Serial Link No.
1 - 33
33
Common Address 1
Not Used
Not Used
Common address 2
Not Used
Not used
Common address 3
Not used
Not used
SYSTEM PARAMETER SETTINGS
Line Voltage
100v-22kv
415v
VT Primary
Not Connected, 100v-22kv
Not Connected
VT Secondary
" " , 95-660v
" "
Motor FLC
1-2000A
100A
CT Primary
1-2000A
100A
E/F CT Primary
1-2000A
100A
Earth fault Alarm
1-100% FLC
5% FLC
"
" " Delay
1-60 Sec
10 sec
Earth Fault Trip
1-100% FLC
10% FLC
"
" " Delay
0-2 Sec
0.5 Sec
Current Inhibit
off, 400-1000% FLC
off
Start/Stop Signal
Momentary, Maintained
Momentary
Starting Method
DOLNR,Star/Delta,Reversing
DOLNR
2 Speed,Valve Control
Max Time in Star
1-60 Sec
10 Sec
Transition Time
0.05-2.0 Sec
0.2 Sec
Star to Delta at
75-200% FLC
150% FLC
Low Speed FLC
1-2000A
10A
Low Speed t6X
0.5-120Sec
10 Sec
Designate Aux 1
Alarm,Contactor A, Contactor B, Run
Alarm
Aux 1 Delay
0-120 S e c
0
Designate Aux 2
Trip, Trip Fail Safe, Contactor A,
Trip
Contactor B
Aux 2 Delay
0-120 Sec
0
Protection Only
Yes, No
No
VOLTAGE SETTINGS
Undervoltage Setting
50-95%
80%
Undervoltage Delay
0.2-10 Sec
5
S e c
Undervoltage Restart
Yes,No
No
Undervoltage Restart Delay
0.2-120 Seconds
Overvoltage Alarm
100-120%
115%
Overvoltage Trip
100-120%
120%
Overvoltage Trip Delay
1-100 Sec
1 Sec