45
■
Controller Number Setting
Set this switch always to 1 when using the System
Controller in a system including a Multiplexer WJ-
FS616/FS616C.
●
Switch Setting Procedures
1. Remove the DC plug from the rear of the controller.
2. Set the MODE switch referring to the table.
• The bit switches #1 to #3 should be set to positions that
match the version of the Multiplexer installed in the sys-
tem.
• Bit 5 opens or terminates the communication chain. The
switch should be set to OFF when the controller is locat-
ed in an intermediate position of the chain.
• Bit 6 specifies either Operator or Administrator as the
operation mode. Set to Administrator when setting up
the controller.
• Bits 4, 7 and 8 are reserved.
3. Set the CONTROLLER NO. switch to 1.
4. Connect the DC plug to the controller.
●
Unit Version
The unit ID is defined by the upper 3 bits depending on the
software version installed in the unit.
• WJ-FS616
• WJ-FS616C
MODE
1
2
3
4
5
6
7
8
OFF
ON
MODE
1
2
3
4
5
6
7
8
OFF
ON
0
9
8
7
6
5
4
3
2
1
CONTROLLER No.