43
12 Operation and Control
12.1. Basic Function
Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes,
automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating mode, the
microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature
shifting. The compressor at monobloc unit is operating following the frequency instructed by the microcomputer at monobloc
unit that judging the condition according to internal water setting temperature and water outlet temperature.
12.1.1.
Internal Water Setting Temperature
Once the operation starts, control panel setting temperature will be taken as base value for temperature shifting processes.
These shifting processes are depending on the monobloc unit settings and the operation environment. The final shifted value
will be used as internal water setting temperature and it is updated continuously whenever the electrical power is supplied to the
unit.
12.1.2.
Heating Operation
12.1.2.1. Thermostat control
• Compressor is OFF when Water Outlet Temperature - Internal Water Setting Temperature > 2
°
C for continuously 3 minutes.
• Compressor is ON after waiting for 3 minutes, if the Water Outlet Temperature - Water Inlet Temperature (temperature at
thermostat OFF is triggered) < -3
°
C.
12.1.3.
Tank Mode Operation
Control contents:
• 3 ways valve direction
- 3 ways valve switch and fix to tank side.
• Heat Pump Thermostat characteristic
- Water set temperature = tank set temperature or
[55
°
C]
whichever lower.
- Heat Pump Water Outlet set temperature is set to Maximum (53
°
C) at tank mode
i. Case 1
- THERMO OFF TEMP :
1. THERMO OFF TEMP = Water set tempe
[+2
°
C]
.
2. Tank temperature > THERMO OFF TEMP for continuous 3 minutes, heat pump OFF and water pump OFF.
- THERMO ON TEMP :
1. THERMO ON TEMP = Water set tempe
[-3
°
C]
.
2. When detect tank temperature < THERMO ON TEMP, water pump ON for 3 minute then heat pump ON.
- Pump ON when Tank temperature is less than Tank temperature when Heat Pump Thermo Off -
[-3
°
C]
.
Summary of Contents for WH-MXF09D3E5
Page 10: ...10 4 Location of Controls and Components 4 1 Monobloc Unit ...
Page 11: ...11 4 1 1 Main Components ...
Page 13: ...13 ...
Page 15: ...15 4 1 4 Basic Operation 4 1 5 Advance Operation ...
Page 16: ...16 4 1 6 Weekly Timer Setting ...
Page 17: ...17 5 Dimensions 5 1 Monobloc Unit ...
Page 18: ...18 6 Refrigeration And Water Cycle Diagram ...
Page 19: ...19 ...
Page 20: ...20 7 Block Diagram 7 1 WH MXF09D3E5 ...
Page 21: ...21 7 2 WH MXF12D6E5 ...
Page 22: ...22 8 Wiring Connection Diagram 8 1 WH MXF09D3E5 ...
Page 23: ...23 ...
Page 24: ...24 8 2 WH MXF12D6E5 ...
Page 25: ...25 ...
Page 26: ...26 9 Electronic Circuit Diagram 9 1 WH MXF09D3E5 ...
Page 27: ...27 ...
Page 28: ...28 9 2 WH MXF12D6E5 ...
Page 29: ...29 ...
Page 30: ...30 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 31: ...31 10 1 2 Solar Printed Circuit Board Optional ...
Page 32: ...32 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Page 33: ...33 10 2 1 1 Capacitor Printed Circuit Board 10 2 1 2 Noise Filter Printed Circuit Board ...
Page 34: ...34 11 Installation Instruction Monobloc Unit Dimension Diagram ...
Page 55: ...55 ...
Page 56: ...56 ...
Page 103: ...103 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Page 109: ...109 19 Exploded View and Replacement Parts List 19 1 Refrigerant System ...
Page 110: ...110 ...
Page 114: ...114 19 2 Water System ...