13 Protection Control
13.1. Protection Control For All Operations
13.1.1. Time Delay Safety Control
1. The compressor will not start for three minutes after stop of operation.
13.1.2. 30 Seconds Forced Operation
1. Once the compressor starts operation, it will not stop its operation for 30 seconds.
2. However, it can be stopped using remote control.
13.1.3. Total Running Current Control
1. When the monobloc unit running current exceeds X value, the compressor frequency will decrease.
2. If the monobloc unit running current does not exceed X value, the compressor frequency will return to normal operating
frequency.
3. If the monobloc unit running current continue to increase till exceed Y value, compressor will stop, and if this occurs 3 times
within 20 minutes, system will stop operation and OFF/ON remote control LED will blink (F16 error occurs).
13.1.4. IPM (Power transistor) Prevention Control
A. Overheating Prevention Control
1. When the IPM temperature rises to 95
°
C, compressor will stop immediately.
2. Compressor will restart delay 3 minutes when the IPM temperature decreases to 90
°
C.
If this condition repeats continuously 3 times within 30 minutes, system will stop operation and OFF/ON remote control LED
will blink (F22 error occurs).
B. DC Peak Current Control
1. When the current to IPM exceeds set value of 49A +/- 5A for MXF09D & MXF12D, compressor will stop. Compressor will
restart after three minutes.
2. If the set value exceeds again for more than 30 seconds after the compressor restarts, operation will restart after two minutes.
3. If the set value exceeds again for within 30 seconds after the compressor restarts, operation will restart after one minute. If
this condition repeats continuously for seven times, system will stop operation and OFF/ON remote control LED will blink (F23
error occurs).
13.1.5. Compressor Overheating Prevention Control
• The compressor operating frequency is regulated in accordance to compressor tank temperature as shown in below figures.
When the compressor tank temperature exceeds 112
°
C, compressor will stop, and if this occurs 4 times within 30 minutes,
system will stop operation and OFF/ON remote control LED will blink (F20 error occurs).
MXF09D3E5
MXF12D6E5
Operation Mode
X
Y
X
Y
Heating
24.0
29.8
28.0
29.8
Summary of Contents for WH-MXF09D3E5
Page 10: ...10 4 Location of Controls and Components 4 1 Monobloc Unit ...
Page 11: ...11 4 1 1 Main Components ...
Page 13: ...13 ...
Page 15: ...15 4 1 4 Basic Operation 4 1 5 Advance Operation ...
Page 16: ...16 4 1 6 Weekly Timer Setting ...
Page 17: ...17 5 Dimensions 5 1 Monobloc Unit ...
Page 18: ...18 6 Refrigeration And Water Cycle Diagram ...
Page 19: ...19 ...
Page 20: ...20 7 Block Diagram 7 1 WH MXF09D3E5 ...
Page 21: ...21 7 2 WH MXF12D6E5 ...
Page 22: ...22 8 Wiring Connection Diagram 8 1 WH MXF09D3E5 ...
Page 23: ...23 ...
Page 24: ...24 8 2 WH MXF12D6E5 ...
Page 25: ...25 ...
Page 26: ...26 9 Electronic Circuit Diagram 9 1 WH MXF09D3E5 ...
Page 27: ...27 ...
Page 28: ...28 9 2 WH MXF12D6E5 ...
Page 29: ...29 ...
Page 30: ...30 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 31: ...31 10 1 2 Solar Printed Circuit Board Optional ...
Page 32: ...32 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Page 33: ...33 10 2 1 1 Capacitor Printed Circuit Board 10 2 1 2 Noise Filter Printed Circuit Board ...
Page 34: ...34 11 Installation Instruction Monobloc Unit Dimension Diagram ...
Page 55: ...55 ...
Page 56: ...56 ...
Page 103: ...103 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Page 109: ...109 19 Exploded View and Replacement Parts List 19 1 Refrigerant System ...
Page 110: ...110 ...
Page 114: ...114 19 2 Water System ...