14 Servicing Mode
14.1. Test Run
1. Fill up the boiler tank with water. For details refer to boiler tanks installation instruction and operation instruction.
2. Set ON to the monobloc unit and RCCB. Then, for remote control operation please refers to monobloc unit operation
instruction.
3. For normal operation, pressure gauge reading should be in between 0.05 MPa and 0.2 MPa.
If necessary, adjust the water pump speed accordingly to obtain normal water pressure operating range. If adjust water pump
speed cannot solve the problem, contact your local authorized dealer.
14.2. Proper Pump Down Procedure
1. Make sure the OFF/ON remote control LED is OFF (no operation).
2. Press the “PUMPDW” switch on remote control to begin PUMP DOWN mode. Operate the system in PUMP DOWN mode for
10 ~ 15 minutes.
3. After 10-15 minutes, (after 1 or 2 minutes in case very low ambient temperatures (< 10
°
C)), fully close 3 way valve (Liquid
side).
4. After 3 minutes, fully close 3 way valve (Gas side).
5. Press the “OFF/ON” switch on remote control to stop PUMP DOWN mode.
6. Remove the refrigerant piping.
14.3. How To Adjust Water Flow Rate
• Before adjust the water flow rate, make sure that the total water volume in the installation is 30 litres minimum (09C3), 50 litres
minimum (12C6, 14C6 & 16C6).
• The water flow rate can be adjusted with select the water pump speed on the water pump. The default setting is moderate speed
(II). Adjust it to high speed (III) and slow speed (I) if necessary (e.g. reduce the noise of running water).
Below graph shown the external static pressure (kPa) versus water flow rate (l/min).
• Flow rate characteristic of indoor unit is as per above mentioned.
14.4. Expansion Vessel Pre Pressure Checking
• Expansion Vessel with 10L air capacity and initial pressure of 1 bar is installed in this monobloc unit.
• Total amount of water in system should be below 200L.
(Note: This amount of water is not include the tank unit volume)
• If total amount of water is over 200L, please add expansion vessel.
• Please keep the installation height difference of system water circuit within 7m.
(Inner volume of same monobloc unit is about 5L)
Summary of Contents for WH-MXF09D3E5
Page 10: ...10 4 Location of Controls and Components 4 1 Monobloc Unit ...
Page 11: ...11 4 1 1 Main Components ...
Page 13: ...13 ...
Page 15: ...15 4 1 4 Basic Operation 4 1 5 Advance Operation ...
Page 16: ...16 4 1 6 Weekly Timer Setting ...
Page 17: ...17 5 Dimensions 5 1 Monobloc Unit ...
Page 18: ...18 6 Refrigeration And Water Cycle Diagram ...
Page 19: ...19 ...
Page 20: ...20 7 Block Diagram 7 1 WH MXF09D3E5 ...
Page 21: ...21 7 2 WH MXF12D6E5 ...
Page 22: ...22 8 Wiring Connection Diagram 8 1 WH MXF09D3E5 ...
Page 23: ...23 ...
Page 24: ...24 8 2 WH MXF12D6E5 ...
Page 25: ...25 ...
Page 26: ...26 9 Electronic Circuit Diagram 9 1 WH MXF09D3E5 ...
Page 27: ...27 ...
Page 28: ...28 9 2 WH MXF12D6E5 ...
Page 29: ...29 ...
Page 30: ...30 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 31: ...31 10 1 2 Solar Printed Circuit Board Optional ...
Page 32: ...32 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Page 33: ...33 10 2 1 1 Capacitor Printed Circuit Board 10 2 1 2 Noise Filter Printed Circuit Board ...
Page 34: ...34 11 Installation Instruction Monobloc Unit Dimension Diagram ...
Page 55: ...55 ...
Page 56: ...56 ...
Page 103: ...103 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Page 109: ...109 19 Exploded View and Replacement Parts List 19 1 Refrigerant System ...
Page 110: ...110 ...
Page 114: ...114 19 2 Water System ...