12.10. Tank Booster Heater Control
12.10.1. Tank booster heater control
Heating operation condition:
1. Booster heater Turn On condition:
• After BOOSTER HEATER DELAY TIMER fulfil during heat pump startup time in tank mode, or during switching from heating
heat-up interval to tank heat-up interval in heat+tank mode (heating priority not set).
• Tank temperature < tank set tempe
[-5
°
C]
,
• 20 minutes since previous heater off.
* BOOSTER HEATER DELAY TIMER is clear when tank heat-up interval end.
2. Booster heater Turn Off condition:-
• Tank temperature > tank set tempe
[+2
°
C]
for continuous 15 sec
• When BOOSTER HEATER DELAY TIMER start count after switch from heating heat-up interval to tank heat-up interval
* DELAY TIMER can be set by remote control.
12.11. Three Way Valve Control
• Purpose:
- 3 ways valve is used to change flow direction of hot water from heat pump between heating side and tank side
• Control contents:
1. 3 ways valve switch Off:
• During 3 ways valve switch Off time, the hot water will provide heat capacity to heating side.
2. 3 ways valve switch On:
• During 3 ways valve switch On time, the hot water will provide heat capacity to tank side.
3. Stop condition:
• During stop mode, 3 ways valve will be in switch off position
12.12. Sterillization Mode
1. During Sterillization mode, Tank will be heat up to the Sterillize Set temperature for a certain period of time, also set by
controller.
2. The function can only be set on timer to operate once in a week.
3. It will be cancelled even when the temperature is not reached after 4 hours.
4. When tank mode is OFF or disabled, sterillization is cancelled.
12.13. Quiet Operation
• Purpose:
- To provide quiet operation compare to normal operation by reduces monobloc unit noise.
• Starting condition:
1. When quiet button is presses.
2. When quiet request ON time by weekly timer (Refer to remote control.)
• When any of above mentioned condition is achieved, this control is activated.
New target FM speed = Present target FM speed - 80 rpm
Minimum target FM speed = 200 rpm
• Cancellation condition:
1. Cancel by press quiet button
2. Stop by OFF/ON button
Summary of Contents for WH-MXF09D3E5
Page 10: ...10 4 Location of Controls and Components 4 1 Monobloc Unit ...
Page 11: ...11 4 1 1 Main Components ...
Page 13: ...13 ...
Page 15: ...15 4 1 4 Basic Operation 4 1 5 Advance Operation ...
Page 16: ...16 4 1 6 Weekly Timer Setting ...
Page 17: ...17 5 Dimensions 5 1 Monobloc Unit ...
Page 18: ...18 6 Refrigeration And Water Cycle Diagram ...
Page 19: ...19 ...
Page 20: ...20 7 Block Diagram 7 1 WH MXF09D3E5 ...
Page 21: ...21 7 2 WH MXF12D6E5 ...
Page 22: ...22 8 Wiring Connection Diagram 8 1 WH MXF09D3E5 ...
Page 23: ...23 ...
Page 24: ...24 8 2 WH MXF12D6E5 ...
Page 25: ...25 ...
Page 26: ...26 9 Electronic Circuit Diagram 9 1 WH MXF09D3E5 ...
Page 27: ...27 ...
Page 28: ...28 9 2 WH MXF12D6E5 ...
Page 29: ...29 ...
Page 30: ...30 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 31: ...31 10 1 2 Solar Printed Circuit Board Optional ...
Page 32: ...32 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Page 33: ...33 10 2 1 1 Capacitor Printed Circuit Board 10 2 1 2 Noise Filter Printed Circuit Board ...
Page 34: ...34 11 Installation Instruction Monobloc Unit Dimension Diagram ...
Page 55: ...55 ...
Page 56: ...56 ...
Page 103: ...103 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Page 109: ...109 19 Exploded View and Replacement Parts List 19 1 Refrigerant System ...
Page 110: ...110 ...
Page 114: ...114 19 2 Water System ...