16.5.33. Cooling High Pressure Overload Protection (F95)
Malfunction Decision Conditions:
During operation of cooling, when pressure 4.0MPa and above is detected by outdoor high pressure sensor.
Malfunction Caused:
1. Dust accumulation in the outdoor unit heat exchanger.
2. Air short circuit at outdoor unit.
3. 2 way valve closed.
4. Faulty outdoor unit fan motor.
5. Clogged expansion valve or strainer.
6. Excessive refrigerant.
7. Faulty outdoor high pressure sensor.
8. Faulty outdoor unit PCB (main).
Summary of Contents for WH-MXF09D3E5
Page 10: ...10 4 Location of Controls and Components 4 1 Monobloc Unit ...
Page 11: ...11 4 1 1 Main Components ...
Page 13: ...13 ...
Page 15: ...15 4 1 4 Basic Operation 4 1 5 Advance Operation ...
Page 16: ...16 4 1 6 Weekly Timer Setting ...
Page 17: ...17 5 Dimensions 5 1 Monobloc Unit ...
Page 18: ...18 6 Refrigeration And Water Cycle Diagram ...
Page 19: ...19 ...
Page 20: ...20 7 Block Diagram 7 1 WH MXF09D3E5 ...
Page 21: ...21 7 2 WH MXF12D6E5 ...
Page 22: ...22 8 Wiring Connection Diagram 8 1 WH MXF09D3E5 ...
Page 23: ...23 ...
Page 24: ...24 8 2 WH MXF12D6E5 ...
Page 25: ...25 ...
Page 26: ...26 9 Electronic Circuit Diagram 9 1 WH MXF09D3E5 ...
Page 27: ...27 ...
Page 28: ...28 9 2 WH MXF12D6E5 ...
Page 29: ...29 ...
Page 30: ...30 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 31: ...31 10 1 2 Solar Printed Circuit Board Optional ...
Page 32: ...32 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Page 33: ...33 10 2 1 1 Capacitor Printed Circuit Board 10 2 1 2 Noise Filter Printed Circuit Board ...
Page 34: ...34 11 Installation Instruction Monobloc Unit Dimension Diagram ...
Page 55: ...55 ...
Page 56: ...56 ...
Page 103: ...103 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Page 109: ...109 19 Exploded View and Replacement Parts List 19 1 Refrigerant System ...
Page 110: ...110 ...
Page 114: ...114 19 2 Water System ...